Starting up the device - Configuration
Leuze electronic
BCL 604i
64
Input data
Table 10.16:
Input data for module 13
Input data length
2 byte consistent
Output data
None
10.7.5 Module 14 – Interlinked read result
Description
This module is used to switch to a mode in which all decoding results within one reading gate are combined
into a single read result.
Parameter
Table 10.17:
Parameters for module 14
Parameter length
1 byte
Input data
None
Output data
None
10.8 Result Format
In the following various modules for the output of decoding results are listed. They have the same structure
but different output lengths. The PROFIBUS module concept does not cater for modules of variable data
length.
10.8.1 Module 20 – Decoder state
Description
The module indicates the state of the decoding and of the automatic decoder configuration.
Input data
Description
Addr.
Data type
Value range
Init value Unit
Fragment number
Current fragment number
0.0 … 0.3
Bitarea
0 … 15
0
-
Remaining frag
-
ments
Number of fragments which still have to be
read for a complete result.
0.4 … 0.7
Bitarea
0 … 15
0
-
Fragment size
Fragment length, always corresponds to the
configured fragment length, except for the last
fragment.
1
UNSIGNED8
0 … 28
0
-
Parameter
Description
Addr.
Data type
Value range
Default
Unit
Separator charac
-
ter
This parameter is used to define a delimiter
that is inserted between two individual decod
-
ing results.
0
UNSIGNED8
1 … 255
0: No delimiter is used.
’;’
-
An interlinked read result also requires module 12 – Multi-label. In this mode, the additional in
-
formation transmitted in modules 31ff relates to the last decoding result in the chain.
Modules 20 … 27 are, thus, to be regarded as alternatives and should not be used in parallel.
Modules 30 … 40, on the other hand, can be combined freely with the decoding result modules.