35
5
Commissioning
5.3
Fault
5.3.1
Reading Faults
NOTICE!
If you want to read the other display values up to the time of the fault press key 16. All display
values are frozen.
5.3.2
Resetting Faults
5.3.3
Recall Fault History
The ETAMATIC stores the last 10 faults with the associated data of the running time counter.
Requirement: ETAMATIC must not be in fault condition.
CAUTION!
If it is certain that the ETAMATIC has carried a voltage at all times since the last fault, it is pos-
sible, that from the present output of the running time counter and the current time, to deter-
mine at which time the fault occurred.
Red fault LED is on
Press key 17 until "Status" appears.
The display shows a plain text
message (incl. running time counter)
Press key „ENTER“ drücken
Plain text message appears on the
display (incl. output of the running time counter)
Press key RESET
Alternatively:
Use an external switch to send a short signal (min. 2 sec.) to terminal 5.
the error is cleared!
Press key 17 until the display shows "Status".
Press key 3
the display shows the last fault code
Press key 11 (Enter)
the display shows the associated plain text and the run-
ning time hours.
Press key 3 again
The display shows the last but one fault code.
Press keys 3 and 2 to browse through the fault history.
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......