48
6
O2-Control
NOTICE!
The neutral value is obtained from the selected correction mode:
+50%/-50%
neutral value 500 = 50% correction mode
+60%/-40%
neutral value 600 = 60%
The following approximate overall picture results for burner output:
Fig. 6-4 factory settings
Parameter
Factory Settings
901/902
Base value for “Deactivated O
2
trim” = 300
917/918
Base value for "Air deficiency” = 150
No
FMS
ETA
Short Text
Description
Min
Max
Default
897
1
1
O2Stoer
Safety shut-down by O
2
controller / CO controller
allowed? (0-never, 1-when insufficient air)
0
1
0
In case of a fault of the O
2
trim, the O
2
trim will be deac-
tivated. Depending on the cause, the defined correction
value for "deactivated O
2
trim" or "air deficiency" will be
output. The burner does not shut down (content 0).
You can pre-selected, if the burner should shut down in
case of the fault "air deficiency" (content 1).
898
0
0
O2-TotZ
Dead time of O
2
controlled system
3
40
15
Dead time of the O
2
controled system in seconds
Expected values for 2 / 3 -passboiler: 12 seconds
899
0
0
O2-P-Fak
O
2
P-Term
1
50
5
Set the P-term in that way, that the set point value /
actual value deviation of 1...2 vol.% is regulated in 4...6
steps without overshoot.
Setting pulses too short - increase the P-term.
Overshoot - reduce P-term
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......