77
9
Appendix
Fault
Code:
TRD
P425=0
P836>1
EN676
P425=2
P836>1
Description
21.1.11
S506
0
0
Internal comparison: relay out terminal 36 (ETAMATIC K202) not picking up.
S507
0
0
Internal comparison: relay out terminal 41 not picking up.
S508
0
0
Internal comparison: relay out terminal 76 not picking up.
S509
0
0
Internal comparison: Output K203 not picking up.
S510
0
0
Internal comparison: Output K201 not picking up.
S520
0
0
Internal comparison: relay output terminal 67 not dropping out.
S521
0
0
Internal comparison: relay output terminal 43 or 68 (Etamatic) not dropping
out.
S522
0
0
Internal comparison: relay output terminal 16 or 65 (Etamatic) not dropping
out.
S523
0
0
Internal comparison: relay output terminal 11 or 66 (Etamatic) not dropping
out.
S524
0
0
Internal comparison: relay output terminal 45 not dropping out.
S525
0
0
Internal comparison: relay output terminal 68 or 61 (Etamatic) not dropping
out.
S526
0
0
Internal comparison: relay output terminal 36 not dropping out.
S527
0
0
Internal comparison: relay output terminal 41 not dropping out.
S528
0
0
Internal comparison: relay output terminal 76 not dropping out.
S529
0
0
Internal comparison: Output K203 not dropping out.
S530
0
0
Internal comparison: Output K201 not dropping out.
S540
0
0
TRIAC selftest : optical couplers are not OFF
S541
0
0
TRIAC selftest : all TRIACS are not supplied with voltage!
S542
0
0
TRIAC selftest : main gas 1 is currentless
S543
0
0
TRIAC selftest: main gas 2 is currentless
S544
0
0
TRIAC selftest : oil pump is currentless
S545
0
0
TRIAC selftest : oil valve is currentless
S546
0
0
TRIAC selftest : Ignition transformer is currentless
S547
0
0
TRIAC selftest : ignition valve is currentless
S550
0
0
Oil fuel blocked because a required solenoid valve is not connected
S551
0
0
Gas fuel blocked because a required solenoid valve is not connected
S552
0
0
No valve connected? Check fuse F3 and F4
S600
0
0
Program check time of sequencer expired.
S601
0
0
Leak check fault: gas pressure still applied.
S602
0
0
Leak check fault: gas pressure missing.
S603
0
0
Vent gas line manually.
S604
0
0
Flame signal not arriving in time.
S605
>88
3
Oil pressure < min !!!
S606
1
1
Gas > min appears in oil operation.
S607
1
1
Ignition position acknowledgement dropping.
S608
0
0
Boiler safety chain dropping.
S609
1
1
Gas safety chain dropping.
S610
>88
3
Oil safety chain dropping.
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......