
45
6
O2-Control
6.11.5
Calling up the Set Correction Mode
Take the correction into account during later programming.
The correction actuator must be able to operate without the ETAMATIC reaching the end-stop
(0 or 999 or limit stop values).
If the correction actuator cannot be driven all the way as required because a channel has
reached the range limit determined during pre-ventilation, the burner's output is increased or
decreased until the actuator can be driven all the way.
6.11.6
Checking the Combustion Boundary Values
It is necessary to guarantee the combustion facility's safe burning even with the maximum cor-
rection applied. The correction value can be modified as follows in order to set the correction
range and monitor the combustion boundary values.
Adjustment of the correction range is possible in parameter 517. If you adjust parameter 517
while the burner is running, adjust in small steps and pause between two steps. Otherwise the
fault 106 may occur.
NOTICE!
The burner must be ON and the control release must be set.
Example:
20 - 100 is a typical correction range for O
2
trim.
This means: With a correction mode from +60% to -40% (factory set-
ting), the control range, which is adjustable via the correction during
correcting to se120; -80...+60; -40; (in digit)
Recommendation: You should chose the correction mode and the correction range in
that way, that the correction effect on the O
2
value is -2 to 3 vol.% O
2
in direction excess air, and 1 to 1.5 vol.% O
2
in direction air deficiency.
Press key 1 "RESET"
Press key 11 "ENTER“ to confirm.
Press key 1 RESET
Enter password (see chapter 5.1.2 Password Entry)
Select "Set O
2
” via keys 13 and 14
Confirm query with key 8
Set load value with keys 16 and 17
Press key 11 ENTER.
Press key 5
The display shows "TK".
Use keys 2 and 3 to modify the correction value within the burner running.
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......