24
5
Commissioning
5.1.12
Delaytime of the Air Dampers During Pre-ventilation
Select parameter no. 768.
No
FMS
ETA
Short Text
Description
Min
Max
Default
768
1
2
KverznLE
Damper delay after fan ON in seconds
0
15
5
Delay time for flaps after switching ON the fan in sec-
onds (only for FAT)
Enter a delay time for opening of the flaps with respect
to the ventilator release. This prevents from increasing
the power consumption of the ventilator motor in the
star/delta starting phase (only effective for FMS and
ETAMATIC).
(from 5.4 / 52201 on)
This parameter affects even with continuous ventilation.