124
9
Appendix
9.25
Technical Data
Power supply
from 115 V - 15% to 230 V +10% 50/60 Hz
To be used only in a grounded power line network!
Power
Consumption
approx. 50 VA
Ambient
Temperature
normal ope 0°C … + 60°C
transport and storage:-25°C … + 60°C
Display
alphanumeric display, 2 rows with 16 digit each
Permissible
Ambient Humidity
class F, DIN 40 040
Protection Class
IP 54 (with sealing against cabinet door), otherwise IP 20
In- and Outputs
14 digital inputs 24V
16 digital inputs 230V
1 analogue inputs (ETAMATIC S S)
3 analogue inputs - all non-floating
Digital Signal
Inputs
The parasitic capacitance of the lead connected to the digital inputs may not exceed 2.2µF as
a result of the ETAMATIC self-tests. The lead length should be limited to 100 m. Since the dig-
ital inputs are for 24V DC, suitable contacts for that voltage should be used (hard silver or gold-
plated)
Regular Firing Rate
Input
By actual load power control unit. By means of PT 100 direct connection, manual operation is
possible via three-point switch signal.
Feedback Inputs
Potentiometer 5k
or current signal 0/4 … 20 mA (ETAMATIC S channel 1)
Optional: Direct switching of Namur transmitter
Control Outputs
4
Resolution
999 digit, 10 bit
Three-point-step
running time of the actuating drives: 30s...60s
possible servomotors:
6 Nm 60 sec. running time to 90° Type: 6 62 R 2127
19 Nm 60 sec. running time to 90° Type: 6 62 R 2111/N
30 Nm 60 sec. running time to 90° Type: 6 62 R 2112
40 Nm 60 sec. running time to 90° Type: 6 62 R 2121
You may only use other servomotors with the permission of LAMTEC.
Current consumption max 50 mA continuous current.
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......