Appendix
WARNING!
P 762 = 0
terminal 46 has no function (ETAMATIC OEM and Burner Control FA1!
P 17 = 3 (FA1 special)
terminal 46 is set to "ignition position acknowledgement!
"Oil pressure > min" / "atomiser air pressure" is not monitored via terminal 46!
You must monitor these signals with the safety interlock chain oil via terminal 51!
47
gas pressure>min
(leakage test)
gas pressure>min
(leakage test)
gas pressure>min
(leakage test)
gas pressure>min
(leakage test))
46
ignition position
acknowledgement
P 762
0 = no function
1 = oil pressure>min /
atomiser air pressure
P 18
0 = oil pressure>min
(atomiser)
1 = atomiser air pres-
sure (rotation atomiser)
P 762
0 = no function
1 =oil pressure>min /
atomiser air pressure
P 18
0 = oil pressure>min
(atomiser)
1 = atomiser air pres-
sure (rotation atomiser)
ignition position
acknowledgement
No
FMS
ETA
Short Text
Description
Min
Max
Default
18
2
2
ÖlpumpON
oil pump ON, 0=standard, 1=together with the fan
0
1
From version 4.2 on
0 = pressure atomiser,
ignition transformer switches output “oil pump” on
and terminal 46 is set to “oil pressure > min”
(ETAMATIC OEM and FA1 only)
1 = rotation atomiser
fan switches on the output “oil pump”
and terminal 46 is set to “atomizer air pressure”
(ETAMATIC OEM and FA1 only)
762
2
4
Fkt.Kl.6
Function terminal 6: 0-recirc. ON signal / 1-oil pressure
> min signal
0
1
0
ETAMATIC:
0 = no function
1 = no function / if P788 = 1, then "recirculation ON"
via PROFIBUS
FMS - terminal 6:
0 = "recirculation ON"
If the recirculation signal is missing during operation,
the recirculation channel remains closed or runs
close.
If P 427 (VODelR) = 0 the recirculation channel
remains close at the pre-ventilation period.
1 = "oil pressure > min"
The internal recirculation signal has always the
state 1.
ETAMATIC OEM / Burner Control FA1 - terminal 46:
0 = no function
1 = "oil pressure>min" with pressure atomiser (P 18 = 0)
or "atomiser air pressure" with by rotation atomiser
(P 18 = 1)
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......