107
9
Appendix
9.14
Inernal Connecting Diagram of the Control Output Device
Fig. 9-21 Internal connecting diagram of the control outputs
Always connect the attached loads (valves etc.) to the ETAMATIC (even when the burner is
off). If You could not ensure this, use an RC combination (ca. 0,15µF, ca. 220
) between the
output terminal and neutral to let the testing current flow.
WARNING!
Connect the valves directly to the terminal. The activating current of the load must be much
higher than 9mA
Fig. 9-22 Example: safety interlock chain wiring via 230 V
No.
Description
1
ETAMATIC
2
230 V contacts safety interlock chain
3
optional unlocking switch