Appendix
Setting of the sensitivity of the flame scanner FFS 06 and FFS 05 (IR,UV)
Adjust sensitivity with switch S1 and S2. You will find the switches after opening the scanner’s
housing.
WARNING!
Do not open FFS 06 UV!
Fig. 9-1 FFS 05 Adjusting the flame sensitivity - factory settings IR 50% UV 100%
Fig. 9-2 FFS06 There is no sensitivity switch for flame scanner type FFS 06-UV
9.2.2
General Information of the Optical Flame Monitoring
Notes on assembly and installation
The processes that occur during combustion give rise, inter alia, to a pulsing component of
the flame's radiation (flame flickering), whose oscillations (flame frequency) are relatively rap-
id at the flame's root (i.e. near the burner's mouth) and become slower toward is tip.
For individual monitoring, the flame sensor should be aligned in that way, that the first third of
the flame is observed.
The flame sensor's correct alignment is essential for achieving a high degree of availability
and/or selectivity.
WARNING!
We recommend to lay the supply cable, including their extension, on separate cable trays to
keep mains and control lines as well as high-energy power lines and equipment separated
from each other (e.g. ignition lines, ignition transformer, electrical motors, contactors). More-
over, avoid any parallel cable routing together with mains cables in trays
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......