25
5
Commissioning
5.1.13
Parameters of the Interface
NOTICE!
These parameters have to be equal to the settings of the remote control software.
Otherwise no communication is possible.
5.1.14
Deactivate leakage test
Select parameter no. 772
No
FMS
ETA
Short Text
Description
Min
Max
Default
822
2
2
Baud S1
Baud rate of serial interface 1
0
5
4
This parameter sets the baud rate for the serial inter-
face. The standard value is parameter content "4"
(19,200 baud). If the display shows problems with the
serial transmission (especially with long serial connec-
tions), it may be helpful to drop the baud rate. This must
be carried out on the VMS/FMS/ETAMATIC as well as
on the operating device e.g. laptop.
0 = 1200 Baud 3 = 9600 Baud
1 = 2400 Baud 4 = 19 K 2 Baud
2 = 4800 Baud 5 = 38 K 4 Baud*
824
2
2
Par. S1
Parity check for serial transfer (ser.1)1
0
2
1
This parameter sets the parity bit for interface transmis-
sion. Standard is even (parameter content: EVEN=0,
NONE=1, ODD=2).
0 = even
1 = none
2 = odd
826
2
2
Adr. S1
Network address VMS/FMS (ser.1)1
0
31
1
Network address VMS / FMS (serial Interface 1)
Enter the network address for the serial interface. Fac-
tory status for the network address is "1". Only if several
devices are connected via an RS422/RS485 bus, this
network address has to be changed.
No
FMS
ETA
Short Text
Description
Min
Max
Default
722
1
4
Laufz K
Running time in points/mins. for continuous output
channel 4
see P 719
0
65535
9999
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......