44
6
O2-Control
Fig. 6-2 Correction to the setpoint
NOTICE!
When switching on any O
2
correction you must ensure, that the combustion boundary values
are maintained even with the maximum possible correction (100%). For details see chapter
6.11.6 Checking the Combustion Boundary Values.
Correction type 2 is used where the correction is applied to a non-linear control element, e.g.
air damper. The curve's slope is taken into account before calculating the correction. A flatter
curve results in a smaller correction range, whilst a steeper curve results in wider range.
6.11.3
Correction Type 2
Correction mode: Effect to load axis +60% to -40%
Fig. 6-3 correction type 2
6.11.4
Setting the Correction Range
Use parameter 517 to adjust the correction range from 0 to 999.
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......