81
9
Appendix
9.5
Aides
A13
Fault 105
During the check of the redundant curves an error was identified.
If data were provided via PC interface:
Enter curve data again for the corresponding curve set
if this is not possible:
select appropriate curve set
Clear memory
Re-enter curve
A 14
Fault 106
In checking the redundant parameters an error was identified
If data were provided via computer interface:
Read in parameter again
if this is not possible:
select the parameter
check displayed value and if necessary modify it
In order to restore the parameter, a change must be made. If the correct value is displayed,
change it for one digit and change it back again.
If several parameters are defective, repeat as necessary.
If the parameter is not included in your release level, you must request an EEPROM from
LAMTEC
A20
Fault 370
The internal communication is not functioning.
Voltage off and back on
After changing EPROM:
Check whether the monitoring program EPROM is correctly inserted
otherwise:
Change processor card.
A21
Fault 901, 904, 905,
906, 911, 912, 913,
914, 915
After changing a potentiometer, the reference must be entered again.
Voltage levels are checked in the device. These can give rise to false errors as a result of in-
correct external wiring.
Check wiring
In the case of analog inputs the reference element serves for voltage supply to the potentiom-
eters.
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......