123
9
Appendix
9.24.1
Example of a Protocol of the Parameter Settings of the Monitoring Bands
Date:
Serial No.:
Installation:
Operating mode:
Tolerance on air shortage side:
Channel Functions
Dead band
Monitoring Band
Band shift
Channel 1
356
32 /34
62 / 67
708
Channel 2
357
33 / 43
63 / 73
709
Channel 3
358
34 / 35
64 / 74
710
Channel 4
359
35 / 45
65 / 75
711
Channel 5
360
36 / 46
66 / 76
712
Adjustment in
air deficiency
direction
Adjustment in
excess air
direction
Correction
range
Correction value
with O
2
control
deactivated
correction value
with air deficiency
Default setting 40: 60
(cross out, if not applicable)
1.
The dead band on the air shortage side is always 0 digit
2.
The band shift is at least as large as the monitoring band in the air deficiency direction.
3.
If the combustion air fan has speed control, the monitoring band on the air deficiency side is 0 digits.
4.
The following applies if 1. and 2. and, if applicable, 3. are satisfied: there is no tolerance on the air shortage side, therefore
the shut-off limits in the air shortage direction do not have to be tested.
5.
A test has not been performed with regard to excess air because
..........................................................................................................................................................................
*
6.
It should be ensured that, if the O
2
regulator is deactivated, the burner is operated with more excess air than when operat-
ing onthe required value curves (corresponding to the burner setting protocol)
I have checked the facts above.:......................................................................................................................................................
company name date signature
*
If this phrase has been deleted a test protocol on the shut-off limits for excess air should be submitted.
Summary of Contents for ETAMATIC
Page 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Page 2: ......
Page 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Page 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Page 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Page 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Page 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Page 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Page 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Page 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Page 134: ...133 9 Appendix...
Page 135: ......