36
TP-6694
9/20
Description
Controller
Display
Message
Alarm
Horn
Fault
Lamp
Warning
Shutdown
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Low cranking voltage
Lo Crank Vlt
Warning
On
W
Fixed
60%
Fixed
6
Low engine oil level *
Oil Level Low
Warning
On
W
Low engine oil level *
Oil Level Low
Shutdwn
On
S
Low fuel level (diesel models)
*
Fuel Level Low
Warning
On
W
0-100%
35%
0-10
10
Low fuel level (diesel models)
*
Fuel Level Low
Shutdwn
On
S
0-100%
5%
0-10
0
Low fuel pressure (gas
models) *
Fuel Press Low
Warning
On
W
Low oil pressure
Oil Press Low
Warning
On
W
Fixed
(Fixed
inhibit)
0
(30
inhibit)
Low oil pressure
Oil Press Low
Shutdwn
On
S
Fixed
(Fixed
inhibit)
5
(30
inhibit)
No coolant temperature signal
Temp Sig Loss
Shutdwn
On
S
No oil pressure signal
Press Sig Loss
Shutdwn
On
S
Fixed
5
Overcrank
Over Crank
Shutdwn
On
S
Fixed
(30
inhibit)
Speed sensor fault
Spd Sens Flt
Warning
On
W
General Functions
Alarm silence, 0- Auto only
(NFPA 110), 1- Always
Alarm Silence
Mode
S
A
0-1
1
Aux. inputs 0- 5 VDC,
1 analog
Aux Input
Warning
On
W
0-100%
100%
0-10
0
Aux. inputs 0- 5 VDC,
1 analog
Aux Input
Shutdwn
On
S
0-100%
100%
0-10
0
Auxiliary inputs, up to 3 digital
(2 additional digital inputs
available with I/O module
option)
Aux Input
Warning
On
W
0-10
(0-30
inhibit)
0 (0
inhibit)
Auxiliary inputs, up to 3 digital
(2 additional digital inputs
available with I/O module
option)
Aux Input
Shutdwn
On
0-10
(0-30
inhibit)
0 (0
inhibit)
Backup parameters loaded
Backup Pars
Status
Battery charger 1
communication loss
Bat1CommLos
s
On
W
Battery charger 2
communication loss
Bat2CommLos
s
On
W
Battery charger fault * (does
not apply to charger
GM87448)
Batt Chg Flt
On
W
Battery charger identity conflict
BatIdErr
On
W
Battery charger parameter
mismatch
ParMisatch
On
W
Battery fault
Battery Flt
On
W
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
† ECM inputs are engine-manufacturer dependent.
‡ Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST- Short Term, LT- Long Term
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......