134
TP-6694
9/20
Figure 65
4-Input/15-Output Module Customer Connections
Connections
Leads 42A and 2 provide power to the relays. Do not use terminals 42A (+) or 2 (GND) on the controller connection kit terminal
strip to supply voltage to user-supplied accessories. User-supplied DC accessories require separate leads connected directly to
the battery for the voltage supply. Attach user-supplied 12/24-volt DC accessories to the battery positive (+) connection at the
starter solenoid and to the battery negative (-) connection at the engine ground. The 120 VAC accessories require a user-
supplied voltage source.
Note:
A maximum of three inputs may be connected to a single relay driver output. Inputs include dry contacts, remote annunciator,
common failure alarm, A/V alarm, and shunt trip line circuit breaker.
Note:
Only one 4-input/15-output module can be connected to the controller.
P35 4-position jack connects to controller
(factory-connected)
TB5 output connections C and NO for the common
fault relay K15 (other TB5 terminals are factory
connections only)
TB6 8-position terminal block,
digital inputs/digital returns
(D11, D12, D13 and D14)
P36 8-position pin,
analog inputs
TB7 through TB13, connections for relays K1 through K14 with
Normally Open (NO) and Normally Closed (NC) contacts
Battery positive (+) connections (TB5-42A)
CAN connections (TB5-CAN (+)/-CAN (-)
Battery negative (-) connections (TB5-2)
GM97144
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......