2.7.13 Battery Charger 1 and 2
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger cause arcs or sparks.
Locate the battery in a well
‐
ventilated area. Isolate the battery charger from explosive
fumes.
Battery gases. Explosion can cause severe injury or death.
Incorrect use of the equalize charge state may lead to hazardous
situations. Equalization is ONLY applicable for flooded lead acid (FLA) type batteries and will damage gel, absorbed glass mat
(AGM), or nickel
‐
cadmium (NiCad) type batteries. In the controller menu or SiteTech
™ settings, verify that the battery topology
is set correctly for the battery type used. Do not smoke or permit flames, sparks, or other sources of ignition to occur near a
battery at any time.
Battery charger menus are available on Decision-Maker
®
3000 Controllers with controller firmware version 4.8.4 and higher, and
on APM402 controllers.
Battery Charger 1 and 2 menus provide battery charger information and metering. Use this menu to view the charger output
metering and charger states.
Note:
Incorrect charger output system voltage may cause irreversible damage to the battery and abnormal out gassing. Ensure that
the battery charger parameters match the battery manufacturer’s specifications before using. In the controller user interface
settings, verify that the battery topology and system voltage is set correctly for the battery type that is used.
Note:
The battery charger menus are designed to work with charger GM87448. Unless connected to charger GM87448 through CAN
communication, the battery charger menus, although visible, have no effect on the battery charger.
Battery Charger 1 and 2
Battery Charger 1 - - >
Output Volts
Output Amps
Charge State
SFWR Ver
Reduced Out
Temp Comp
Battery Charger 2 - - >
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......