TP-6694
9/20
45
2.4.1
Starting
Local Starting
Press the master control RUN button to start the generator set at the controller.
Note:
The alarm horn sounds and the Not-In-Auto Warning display appears whenever the generator set master control button is not
in the AUTO mode.
Figure 10
Master Control Button Function Summary
Note:
The transient start/stop function of the controller prevents accidental cranking of the rotating engine. The generator set stops
and recranks when the OFF/RESET button is momentarily pressed and then the RUN button is pressed.
Auto Starting
Press the master control AUTO button to allow startup by the automatic transfer switch or remote start/stop switch (connected
to controller terminals 3 and 4).
Terminals 3 and 4 connect to a circuit that automatically starts the generator set crank cycle when an external source closes the
circuit.
Note:
The controller provides up to 30 seconds of programmable cyclic cranking and up to 60 seconds rest with up to 6 cycles. The
default setting is 15 seconds cranking and 15 seconds rest for 3 cycles. Make cyclic cranking adjustments using SiteTech™
software.
Prime Power Switch
The controller has an optional prime power mode of operation. The prime power mode requires installation of an optional prime
power switch kit. See the section titled: Accessories, for instructions on how to install the optional prime power switch kit. The
prime power switch kit prevents engine starting battery drain when the generator set is shut down and no external battery
charging is available.
Move the prime power switch located on the junction box to the CONTROLLER ON position before attempting to start the
generator set. When the prime power mode is off, all controller functions including the digital display, LEDs, and alarm horn are
operative.
Stop the generator set using the stopping procedures in the section titled: Stopping (User Stopping and Fault Shutdown) before
placing the generator set in the prime power mode. Move the prime power switch located on the junction box to the
Button
Mode
Generator
Set Status
Button Lamp
Fault Lamp
Alarm
Horn
Alarm Silence
Button *
Alarm Silence
Lamp
Controller Display
AUTO
Off
Green
—
Off
—
—
Scrolling Overview
Menu Only
On (or
Cranking)
—
Off
—
—
Running and
then Off
Red
On
—
—
Shutdown Message
Off
Pressed
Yellow
OFF/RESET
Off
Red
Yellow
On
—
—
Not in Auto Warning
Off
Pressed
Yellow
RUN
(unit fails to
start)
Off (or
Cranking)
Yellow
Yellow
On
—
—
Not in Auto Warning
Off
Pressed
Yellow
Off
Red
On
—
—
Locked Rotor
Shutdown (or other
shutdown message)
Off
Pressed
Yellow
RUN
(unit starts)
Off (or
Cranking)
Yellow
Yellow
On
—
—
Not in Auto
Warming
On
Off
Pressed
Yellow
Running and
then Off
Yellow
Red
On
—
—
Shutdown Message
Off
Pressed
Yellow
* Alarm silence only works when in the Auto mode unless the Always selection is made using SiteTech
™.
Refer to the section titled: GenSet System for more information
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......