146
TP-6694
9/20
Fault and Status Condition
Fault LED
System Monitoring LEDs and Functions
System
Ready
LED
Generator
Running LED
Communications
Status LED
Common
Fault
LED
Common
Fault
Output
Horn
Overcrank (Shutdown)
Red SF
Red SF
Off
Green
Red SF
On
On
High Engine Temperature (Warning)
Yellow SF
Red SF
Green
Green
Yellow SF
On
On
High Engine Temperature (Shutdown)
Red SF
Red SF
Off
Green
Red SF
On
On
Low Oil Pressure (Warning)
Yellow SF
Red SF
Green
Green
Yellow SF
On
On
Low Oil Pressure (Shutdown)
Red SF
Red SF
Off
Green
Red SF
On
On
Overspeed (Shutdown)
Red SF
Red SF
Off
Green
Red SF
On
On
Emergency Stop
Red SF
Red SF
Off
Green
Red SF
On
On
Low Coolant Level/Aux (Shutdown)
Red SF
Red SF
Off
Green
Red SF
On
On
Low Coolant Temperature
Yellow SF
Red SF
Green or Off
Green
Yellow SF
On
On
Low Fuel (Level or Pressure)
Yellow SF
Red SF
Green or Off
Green
Yellow SF
On
On
Low Cranking Voltage
Yellow SF
Red SF
Off
Green
Yellow SF
On
On
Battery Voltage (Hi)
Yellow
Red SF
Green or Off
Green
Yellow SF
On
On
Battery Voltage (Lo)
Yellow SF
Red SF
Green or Off
Green
Yellow SF
On
On
Battery Charger Fail
Yellow SF
Red SF
Green or Off
Green
Yellow SF
On
On
Common Fault (Warning)
Yellow SF
Green
Green or Off
Green
Yellow SF
On
Off
Common Fault (Shutdown)
Red SF
Green
Green or Off
Green
Red SF
On
On
User-Defined Digital Input 1 (Warning)
Yellow SF
Green
Green or Off
Green
Off
Off
Off
User-Defined Digital Input 1
(Shutdown)
Red FF
Green
Green or Off
Green
Off
On
On
User-Defined Digital Input 2 (Warning)
Yellow SF
Green
Green or Off
Green
Off
Off
Off
User-Defined Digital Input 2
(Shutdown)
Red FF
Green
Green or Off
Green
Off
On
On
User-Defined Digital Input 3 (Warning)
Yellow SF
Green
Green or Off
Green
Off
Off
Off
User-Defined Digital Input 3
(Shutdown)
Red FF
Green
Green or Off
Green
Off
On
On
User-Defined Digital Input 4 (Warning)
Yellow SF
Green
Green or Off
Green
Off
Off
Off
User-Defined Digital Input 4
(Shutdown)
Red FF
Green
Green or Off
Green
Off
On
On
User-Defined Digital Input 5 (Warning)
Yellow SF
Green
Green or Off
Green
Off
Off
Off
User-Defined Digital Input 5
(Shutdown)
Red FF
Green
Green or Off
Green
Off
On
On
ATS Position N (RSA III with ATS only)
Green
Green
Green or Off
Green
Off
Off
Off
ATS Position E (RSA III with ATS only)
Red
Red SF
Green or Off
Green
Off
Off
Off
ATS Available N (RSA III with ATS
only)
Green
Green
Green or Off
Green
Off
Off
Off
ATS Available E (RSA III with ATS
only)
Red
Red SF
Green or Off
Green
Off
Off
Off
ATS Test (RSA III with ATS only, Test
initiated at ATS)
Yellow
Green
Green or Off
Green
Off
Off
On
ATS Test (RSA III with ATS only, Test
initiated at RSA)
Green
Green
Green or Off
Green
Off
Off
On
ATS Fault (RSA III with ATS only, No
fault)
Green
Green
Green or Off
Green
Off
Off
On
ATS Fault (RSA III with ATS only, With
fault)
Red FF
Red SF
Green or Off
Green
Off
Off
On
EPS Supplying Load
Green
Green
Green or Off
Green
Off
Off
Off
Not-In-Auto
Red FF
Red SF
Off
Green
Yellow SF
On
On
Communication Status (Loss - Master)
Red FF
Off
Off
Red FF
Off
On
On
Communication Status (Loss - Slave)
Red SF
Off
Off
Red SF
Off
On
On
Note:
SF = Slow Flash (once per second), FF = Fast Flash (five times per second)
Figure 82
RSA III System Monitoring LEDs and Functions
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......