40
TP-6694
9/20
Description
Controller
Display
Message
Alarm
Horn
Fault
Lamp
Warning
Shutdown
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Charger Voltage Absorption (V)
S
A
13
–15
(12 V)**
26
–30
(24 V)**
14.25
(12 V)
28.5
(24 V)
Charger Voltage Bulk (V)
S
A
13
–15
(12 V)**
26
–30
(24 V)**
14.25
(12 V)
28.5
(24 V)
Charger Voltage Equalize (V)
Note
:
Equalize is only available with
FLA/VRLA topology selected.
A
14
–16
(12 V)
28
–32
(24 V)
Charger Voltage Float (V)
S
A
13
–14
(12 V)**
26
–28
(24 V)**
13.25
(12 V)
26.5
(24 V)
Current transformer ratio ‡
S
S
1-
1200
ECM power
S
S
0-1
0
Engine cooldown delay
S
A
0-600
300
Engine (cyclic) crank on
S
A
10-30
15
Engine (cyclic) crank pause
S
A
1-60
15
Engine ECM start delay
S
A
0-300
0
Engine idle duration
S
A
0-60
60
Engine no. of (cyclic) crank
cycles
S
S
1-6
3
Engine restart delay
S
A
1-10
10
Engine start aid delay
S
A
0-10
0
Engine start delay
S
A
0-300
0
Equalize Current Limit (A)
Note:
Equalize is only available with
FLA/VRLA topology selected.
S
A
1
–5
Forced Charge Cycle Reset
S
A
Active
Inactive
Inactive
Output Enable
Fixed
Active
System battery voltage ‡
S
S
12-24
12
Voltage regulator gain
S
R
1-255
128
Voltage regulator stability
adjust
S
R
1-255
128
Voltage regulator, volts per
Hertz slope
S
R
1-10
5
Voltage regulator, volts per
Hertz cut in frequency
S
R
42-62
57.5
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
† ECM inputs are engine-manufacturer dependent.
‡ Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST- Short Term, LT- Long Term
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......