TP-6694
9/20
23
Oil Pressure
displays the engine oil pressure. This value also shows in the Overview Menu.
Coolant Temperature
displays the engine coolant temperature. This value also shows in the Overview Menu.
Fuel Level
% displays the fuel tank level for diesel-powered models if so equipped. This value also shows in the Overview
Menu.
Battery
displays the DC voltage of the engine starting battery(ies). This value also shows in the Overview Menu.
Fuel Pressure
displays fuel pressure for some engines. Refer to the Appendix, Controller Displays from the Engine ECM. This
value also shows in the Overview Menu.
Generator Metering Menu
Total Power kVA and kW
displays alternator output as actual output values.
Rated Power
displays alternator output as a percentage of the entered data value.
Volts
displays the alternator output AC voltages. The display shows all line-to-line and line-to-neutral voltage combinations for
three-phase or single-phase configurations.
Current
displays the alternator output AC amps. The display shows each line (L1-L2-L3) of three-phase models or L1-L2 current
for single-phase models.
Frequency (Hz)
value displays for the output AC voltage. This value also shows in the Overview Menu.
Reset Calibration
providing the means to reset the configuration values is available in this menu.
The calibration values are reviewable at all times and provide the calibration of the voltage and current sensing logic. Changing
the system voltage or replacing the circuit board requires a calibration adjustment.
To enable calibration, start the generator set and select the
Volts L1-L2
display. Then push and hold the pushbutton/rotary
selector dial until the
Calibration Enabled
popup appears. Calibration of each display is now available. The display will show the
following values for three-phase generator sets. Single-phase generator sets will only display items marked (*).
Volts L1-L2 *
Volts L2-L3
Volts L3-L1
Volts L1-N *
Volts L2-N *
Volts L3-N
Current L1 *
Current L2 *
Current L3
The user can change individual values or can select
Reset Calib?
-Yes to reset all values. The
Reset Calib?
display will only
show if calibration is enabled. Refer to the requirements shown with Generator Set Calibration in the section titled: Status and
Notice Digital Displays.
To disable calibration, rotate the pushbutton/rotary selector dial until the
<-Return
popup appears. Momentarily press the
pushbutton/rotary selector dial. Stop the generator set if not already done.
Generator Set Information Menu
GenSet M/N
displays the generator set model number.
GenSet S/N
displays the generator set serial number.
Controller S/N
displays the controller serial number.
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......