138
TP-6694
9/20
6.1.6
Two-Input/Five-Output Module
The two-input/five-output module provides a generator set mounted panel with two analog or digital inputs and five digital outputs.
See Figure 70 for circuit board components and electrical connections to the controller.
See Figure 71 for connections of analog inputs.
See the following subsection, Accessory Connections, for terminal identification.
Use a computer with Kohler SiteTech™ software to assign functions to digital outputs. Each input and output corresponds to a
controller connection. Verify that the settings are appropriate for the connected sensor, switch, or equipment.
Refer to Introduction
—List of Related Materials for the SiteTech™ Software Operation Manual part no.
SiteTech™ analog inputs B1 and B2 and digital outputs B1 through B5 are designated for use on the optional two-input/five-
output module. See Figure 69.
SiteTech I/O Name
Optional I/O Module Connection
Analog Input B1
Analog Input B2
P28 Analog Input VN1/VP1
P28 Analog Input VN2/VP2
Digital Output B1
Digital Output B2
Digital Output B3
Digital Output B4
Digital Output B5
P29 (K1)
P30 (K2)
P31 (K3)
P32 (K4)
P32 (K5)
Figure 69
Input/Output Assignments
Figure 70
Two-Input/Five-Output Module Board
Figure 71
Analog Input Connections P28
P29/P30/P31 K1/K2/K3 2-amp relay outputs
P32 K4/K5 10-amp relay outputs
SW1 switch
P28 In1/In2 analog or digital inputs
P25 RJ45 In
(APM402/DEC
3000 P23)
P26 RJ45 Out
P27 CAN
terminator
Optional 5 V Power
(50 mA max.)
Optional 5 V Power
(50 mA max.)
100 ohm min. or
50 mA max. current
0-5 Volt Ratiometric Sensor
0-5 Volt Analog
Device
+/- 3 Volt Analog Device
TP-6694-6
P36
+5
VPx
VNx
GND
+5
VPx
VNx
GND
+5
VPx
VNx
GND
P36
P36
Analog
Device
Output
GND
GND
Analog
Device
+
-
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......