Event Log Menu
This menu allows the user to review up to 1000 entries of system events including shutdown faults, warning faults, and status
events. See the section titled: Controller Fault Diagnostics for a list of the items that appear on the Event Log.
Volt Select Menu
Note:
The generator set must be stopped before changing the voltage selection.
This menu allows the user to readily change controller voltage settings. The volt select feature is typically used in towable or
temporary applications.
Note:
The volt select menu requires initial activation by SiteTech™ software. In SiteTech™ software, select True to activate the volt
select menu.
Note:
The generator set output leads require voltage reconnection if the generator set does not have a voltage selector switch installed.
With the generator set stopped, go to the Volt Select menu. Then push and hold the pushbutton/rotary selector dial until the
voltage selection starts to flash. Volt selection is now available. Scroll to the desired voltage and momentarily press the
pushbutton/rotary selector dial to confirm the voltage selection.
The displays for
Volt Select
appear as shown in the following list.
120/240 V 1 Ph
120/208 V 3 Ph
139/240 V 3 Ph
277/480 V 3 Ph
120/240 V 3 Ph
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......