TP-6694
9/20
163
Description
Controller
Display
Message
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Programmer-
Defined
Settings
Charger Depleted
Battery Current Limit
S
A
1
–5
2
Charger Depleted
Battery Voltage Target
S
A
4
–12
(12 V)
18
–24
(24 V)
10 (12 V)
20 (24 V)
Adjustable with
Charger
Custom Profile
enabled.
Charger Equalize Stage
Duration (Min)
Note:
Equalize is only
available with
FLA/VRLA topology
selected.
S
A
60
–480
Charger Manual
Equalize Cycle
Activation
Note:
Equalize is only
available with
FLA/VRLA topology
selected.
S
A
Active
Inactive
Inactive
Charger Maximum
Absorption Time
Threshold (Min.)
S
A
60
–360
60
–600
(NiCad
only)
240
Adjustable with
Charger
Custom Profile
enabled.
Charger Maximum Bulk
Time Threshold (Min)
S
A
60
–600
480
Adjustable with
Charger
Custom Profile
enabled.
Charger Refresh
Charge Cycle Time (Hr)
S
A
0,
23
–672
335
Adjustable with
Charger
Custom Profile
enabled.
Charger Return To Bulk
State Voltage Threshold
(V)
S
A
10
–13
(12 V)**
20
–26
(24 V)**
12.8
(12 V)
25.6
(24 V)
Charger Starter Battery
Topology
Note:
Verify that the battery
topology is set correctly
for the battery type that
is used. Incorrect
charger output system
voltage may cause
irreversible damage to
the battery and
abnormal out gassing.
S
A
Default
FLA/VRLA
AGM Gel
NiCad
Default
Charger System Battery
Voltage
Note:
Verify that the system
voltage is set correctly
for the battery type that
is used. Incorrect
charger output system
voltage may cause
irreversible damage to
the battery and
abnormal out gassing.
S
A
System 12
VDC
System 24
VDC
12 VDC
Charger Temperature
Compensation Enable
S
A
Active
Inactive
Inactive
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......