3.7 Crankcase Ventilation (CCV) Heater Kit GM78171-KP1
Applies to 125/150 kW, 8.1 L GM-powered and 8.8 L PSI-powered generator set models. Consult your local generator set
distributor/dealer for additional information.
The crankcase ventilation (CCV) heater kit provides a controlled heating source to the crankcase ventilation system preventing
freezing water buildup during cold weather. The thermostat turns on at 4°C (40°F) and turns off at 16°C (60°F) reducing energy
consumption. See Figure 46.
Figure 46
Crankcase Ventilation Heater Kit
3.8 Air Cleaner Restrictor Indicator (if equipped)
The air cleaner restriction gauge mounted on the air cleaner(s) helps determine the air cleaner change interval.
The air cleaner restriction gauge monitors air flow and continuously displays restriction readings indicated as vacuum
(see Figure 47). Increased restriction indicates a clogged air cleaner element.
As maximum allowable restriction is reached, the gauge window turns red indicating the air cleaner element needs replacement.
To reset the gauge, push the gauge top down and release.
Figure 47
Restriction Indicators (styles vary)
Heater element
Inline connector
Thermostat
AC power cord
Push down to reset
Display
Gauge window
273113
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......