TP-6694
9/20
29
* Function requires optional input sensors or kits or is engine ECM dependent on some generator set models.
† ECM inputs are engine manufacturer dependent.
‡ The Common Fault Shutdown includes the items marked X‡ in the Shutdown Function column.
Description
Display Message
Warning
Function
Shutdown
Function
Status/
Notice
Relay
Output
General Functions
Alarm horn silenced
(Alarm Silence LED only)
X
Alarm silence, auto only (NFPA 110) or always
AlrmSilence: Auto Only or
AlrmSilence: Always
S
No
Aux. inputs 0- 5 VDC, 1 analog
(2 additional inputs available with I/O module option)
Aux Input Warning
X
X
Aux. inputs 0- 5 VDC, 1 analog
(2 additional inputs available with I/O module option)
Aux Input Shutdwn
X
X
Auxiliary inputs, up to 3 digital
(2 additional inputs available with I/O module option)
Aux Input Warning
X
X
Auxiliary inputs, up to 3 digital
(2 additional inputs available with I/O module option)
Aux Input Shutdwn
X
X
Backup parameters loaded
Backup Pars Status
S
No
Battery charger 1 communication loss
Bat1CommLoss
X
Battery charger 2 communication loss
Bat2CommLoss
X
Battery charger fault * (* does not apply to charger
GM87448)
Batt Chg Flt
X
X
Battery charger identity conflict
BatIdErr
X
Battery charger parameter mismatch
Param Mismatch
X
Battery Fault
Battery Flt
X
Chicago code active
Chicago Code Active
N
X
Common fault
(includes
‡
)
Common Fault Shutdwn
X
N
X
Common warning fault
Common Warng
X
N
X
Default parameters loaded
Default Pars Warning
X
X
Emergency stop
Emerg Stop Shutdwn
X‡
X
Enclosure temperature: high shutdown
Enclsr Temp: High Shutdwn
X
X
Engine cooldown (delay) active
Eng Cooldown Notice
N
X
Engine started
Engine Start Status
S
X
Engine stopped
Engine Stop Status
S
X
EPS supplying load
Emerg Pwr On Notice
N
X
File system error (controller fault)
File Error Shutdwn
X
X
Generator running
Gen Running Notice
N
X
Input/output (module option board) communication
loss
OB1 Com Loss
X
X
Internal failure
Intern Error Shutdwn
X
X
Metering communication loss
MeterCommLos Shutdwn
X
X
NFPA 110 alarm active
NFPA Alarm Notice
N
X
Not in auto (master switch)
Not In Auto Warning
X
X
Remote start
Remote Start Status
S
X
System ready
System Ready Status
S
X
System timer failed
Timer Error Notice
N
X
Generator Functions
AC sensing loss
AC Sens Loss Warning
X
X
AC sensing loss
AC Sens Loss Shutdwn
X
X
Alternator protection
Alt Protect Shutdwn
X
X
Ground fault input *
Ground Fault Warning
X
X
kW overload
Total Power High Shutdwn
X
X
Locked rotor (failed to crank)
Locked Rotor Shutdwn
X
X
Overfrequency
Freq High Shutdwn
X
X
Overvoltage (each phase)
Volts xx- xx High Shutdwn
X
X
Underfrequency
Frequency Low Shutdwn
X
X
Undervoltage (each phase)
Volts xx- xx Low Shutdwn
X
X
(Voltage) regulator communication loss
RegCommLoss Shutdwn
X
X
Summary of Contents for APM402
Page 6: ...6 TP 6694 9 20 ...
Page 16: ...16 TP 6694 9 20 ...
Page 42: ...42 TP 6694 9 20 ...
Page 78: ...78 TP 6694 9 20 ...
Page 112: ...112 TP 6694 9 20 ...
Page 120: ...120 TP 6694 9 20 ...
Page 124: ...124 TP 6694 9 20 Figure 54 20 150 kW Permanent Magnet Single Phase Alternators ADV 5875AB 1 ...
Page 125: ...TP 6694 9 20 125 Figure 55 20 300 kW Permanent Magnet Alternators ADV 5875AB 2 ...
Page 128: ...128 TP 6694 9 20 ...
Page 131: ...TP 6694 9 20 131 Figure 61 Battery Charger to Controller Connections DEC 3000 Controller ...
Page 153: ...TP 6694 9 20 153 Figure 90 Controller Wiring Connections GM78246G 1 ...
Page 154: ...154 TP 6694 9 20 Figure 91 Controller Wiring Connections GM78246G 2 ...
Page 171: ......