Section 3 Troubleshooting
Troubleshooting Chart, continued
Problem
Reference
Corrective Action
Possible Cause
Cranks but
does not
start,
continued
Air cleaner clogged
Clean or replace.
Section 2.4
Magnetic pickup
Check for 1.75 volts or higher from the magnetic pickup during
cranking. A lower signal will cause the stepper motor to open
and close during cranking.
Section 6.9.4
Incorrect controller
configuration
Check for correct controller configuration settings.
Section4.5 or
5.5
Ignition system spark
control or ignition coil
Test and/or replace components.
Engine S/M
Digital spark advance
ignition (DSAI)
connections
(12kW only)
Connect for natural gas. Disconnect for LP.
Check for loose connections.
Section 6.12.5
No engine rotation
sensed (check for an
overcrank fault
shutdown)
Check mag pickup connections, mag pickup gap, and operation.
Section 6.9.4
Check for locked rotor.
Section 6.4
Starts hard
Low battery voltage
Check battery voltage and battery charger connections, power
supply, and operation.
Generator Set
O/M
Air cleaner clogged
Replace element.
Section 2.4
Fuel mixture adjustment
incorrect
Adjust fuel valve.
Section 6.12
DSAI leads incorrectly
connected or
disconnected
(12kW only)
Connect for natural gas. Disconnect for LP.
Section 6.12.5
Spark plug(s)
Replace or regap spark plug(s).
Section 2.3
Spark plug wire(s)
Check spark plug wires and connections. Replace spark plug
wires.
Engine S/M
Ignition components
(spark control or ignition
module)
Test/replace ignition components.
Engine S/M
Insufficient fuel pressure
Check fuel pressure.
Section 6.12.3
Worn piston rings, valves Check compression.
Engine S/M
Starts but
shuts down
Fault shutdown
Check for a fault shutdown code on the controller’s LED display.
Correct the fault and then move the generator set master switch
to OFF/RESET to reset the controller.
Section 4.4 or
5.4
Section 6.11
Stops
suddenly
Fault shutdown
Check for a fault shutdown code on the controller’s LED display.
Correct the fault and then move the generator set master switch
to OFF/RESET to reset the controller.
Section 4.4 or
5.4
Section 6.11
No fuel
Turn on fuel supply.
—
Fuel line restriction
Inspect fuel lines.
—
Fuel lines too long
Check fuel line length.
Section 6.12.1
Air cleaner clogged
Replace element.
Section 2.4
Blown fuse
Check fuses F1, F2 and F3. Replace any blown fuses. If fuse
blows again, test generator components.
Section 6.13
Spark plug(s)
Replace and regap plug(s).
Engine S/M
Engine overheated
(hot engine only)
Check air intake, fuel adjustment, oil level, air inlet/ outlet.
Section 2.5
Section 2.2
Section 6.12
Low oil pressure (LOP)
switch
Attempt startup. If unit shuts down, remove lead from LOP switch
and reset controller. A successful restart attempt indicates a
faulty LOP shutdown switch.
Note:
Check engine oil pressure before performing test and/or
replacing LOP shutdown switch.
Section 2.2.1
Section 6.11.2
Summary of Contents for 12RES
Page 2: ......
Page 6: ...TP 6196 10 09 6 Notes ...
Page 34: ...TP 6196 10 09 34 Section 3 Troubleshooting Notes ...
Page 52: ...TP 6196 10 09 52 Section 4 ADC 2100 and DC 2200 Controllers Notes ...
Page 72: ...TP 6196 10 09 72 Section 5 ADC RES and DC RET Controller Notes ...
Page 100: ...TP 6196 10 09 100 Section 6 Component Testing and Adjustment Notes ...
Page 131: ......