TP-6196 10/09
33
Section 3 Troubleshooting
3.4 Controller Troubleshooting
Refer to the controller troubleshooting table in this
section when troubleshooting procedures in Section 3.3
indicate a possible controller problem. Always check
the ADC-RES controller configuration settings before
replacing the controller.
The installation manual
contains the instructions for checking and changing the
controller configuration.
Possible Cause
Test
Corrective Action
Reference
Controller
Check controller settings. *
Adjust controller settings as required. *
Section 4.5 or
5.5
Check for power to the controller at
lead PF1.
Check/replace fuse F3. Check battery.
Section 8
Check controller fuse F3.
Replace controller fuse.
Section 8
Check controller wiring and
connections.
Tighten connections and/or replace
wiring.
—
Replace SCR module and recheck
voltage.
Replace the SCR module.
Section 6.8
Perform all tests listed under high
output voltage.
Replace the controller only if previous
steps do not solve the problem.
Section 4.9 or
5.9
SCR module
Check wiring and connections to the
SCR module.
Tighten connections and/or replace
wiring to the SCR module.
Section 6.8
Test the SCR module using the
procedure in Section 6.8.
Replace the SCR module and recheck
voltage.
Section 6.8
Check auxiliary winding fuse F1
(lead 55).
Replace auxiliary winding fuse F1
(lead 55).
Section 8
* ADC-RES controller only.
Summary of Contents for 12RES
Page 2: ......
Page 6: ...TP 6196 10 09 6 Notes ...
Page 34: ...TP 6196 10 09 34 Section 3 Troubleshooting Notes ...
Page 52: ...TP 6196 10 09 52 Section 4 ADC 2100 and DC 2200 Controllers Notes ...
Page 72: ...TP 6196 10 09 72 Section 5 ADC RES and DC RET Controller Notes ...
Page 100: ...TP 6196 10 09 100 Section 6 Component Testing and Adjustment Notes ...
Page 131: ......