TP-6196 10/09
68
Section 5 ADC-RES and DC-RET Controller
GM52639
TO RELAY BOARD P14
TO ENGINE HARNESS
TO CONTROL BOARD P11
Figure 5-20
Relay Board Connection Harness GM52639
TB1 Terminal Label
Description
COMMON FAULT NC
Common fault relay normally
closed contact.
Opens on a fault.
COMMON FAULT COM
Common fault relay common
COMMON FAULT NO
Common fault relay normally
open contact.
Closes on a fault.
AUX RUN NC
Auxiliary run relay normally
closed contact.
Open when generator set is
running.
AUX RUN COM
Auxiliary run relay common
AUX RUN NO
Auxiliary run relay normally
open contact.
Closed when generator set is
running.
Note:
Use maximum 14 AWG wire for TB1 connections.
Figure 5-21
TB1 Customer Connections
Contact Ratings
10 A @ 120 VAC
10 A @ 28 VDC
Maximum Operating Voltage
250 VAC/60 VDC
Maximum Switching Capacity
440 VA/75 W
Figure 5-22
Relay Contact Ratings