3-8
BOP HIPWR 091719
Power-up Screen (Power up menu)
•
!
- Save/Recall
•
•
Saved Setups (Figure 3-10): Recall one of 99 saved setups.
•
•
•
Saved Setup Details (Table 3-9): Mode (voltage/current/External), main channel reference (inter-
nal/external/external reference level) and setting, Protection Type (internal/external/LesserLimit) and
setting(s), output status (on/off)
•
@
- Waveform
•
•
Saved Waveforms (Figure 3-11): Choose one of 16 saved waveforms.
•
•
•
New Waveform Settings (Table 3-13): Name (max. 10 characters), mode (voltage/current) No. of cycles,
+Protect, -Protect)
•
•
•
•
First segment: type (Square/ +ramp /-ramp/triangle/sine/level), Frequency, PtoP Amplitude, Offset
•
•
•
Edit Waveform (Figure 3-12): Name, no. of cycles, +protect, -protect, segment list, mode
•
•
•
•
Segment Details (Table 3-12): Type ((ramp/-ramp/triangle/sine/level/slope/trigger),
frequency or period, amplitude, offset, start/stop angle for sine and triangle, Repeat (initial/repeat)
•
#
- Display
•
•
Display Settings (Table 3-3): Graphic Display (
meters
/graphics, background (
black
/white/mono-
black/blue/green/lt.green/ lt.blue), Protect Entry (
independent
/bipolar) Waveform Stop (
outputOFF
/User
Option), Key Press beep (
On
/Off/Error only)
•
$
- Analog Remote Setup (Table 3-16):
•
•
Analog Remote Settings: Reference input (
internal
/external/external reference level), protect limit (
Inter-
nal
/External/LesserLimit), external mode (
disable/
enable)
•
%
- General Setup
•
•
Interface Settings (Table 3-17):
•
•
•
*RST set Output (
on
/off),
•
•
•
GPIB Settings (Table 3-17): Language (
SCPI
/CIIL), GPIB address (default =
6
), Device clear
(
SCPI
/MATE)
•
•
•
Serial Settings (Table 3-17): Baudrate (
Off
/9600/19200/38400), Xon/Xoff (
disable
/enable), prompt (
dis-
abled/echo/
enabled/enab+echo)
•
•
•
LAN Setting (Table 3-18): IP Address, IP MASK, AUTO IP
ON
, DHCP
ON
, Name and index (MDNS
name)
•
•
Max/Min Settings (Table 3-5): for voltage mode: +Voltage max, –Voltage min, ±CProtect max/min; for cur-
rent mode: +Current max, –Current min, ±VProtect max/min
•
•
Load Type (Figure 3-8):
Active
/Resistive/Battery, Remote On-off: (disabled/high is off/low is off/high is
on/low is on/LowPulseOff)
•
•
Remote On/Off (Shutdown or Output On/Off) Operation (Table 2-3):
LowPulse
, HighIsOn, LowIsOn, HighI-
sOff, LowIsOff, Disabled
•
•
Revisions/Test: (Tests: display, keypad, LAN, interface, serial, analog and output)
•
•
Calibration (PAR. 4.4): Voltage, Current and External and Controls calibration. Shows Firmware versions
for Display, Serial, GPIB, LAN and analog.
•
•
Power-up Settings (PAR. 3.3.8): Mode (
Voltage
/Current/External), Main channel Reference (
Inter-
nal
/External/ExtlRefLev), main setting, Protection: Type (
Internal
/External/LesserLimit), Voltage Limit (cur-
rent mode), Current Level (voltage mode), output
ON
/OFF
•
•
Password (See Figure 3-6 for default settings)
•
•
•
Password Settings: Menu protection (Interface/Max-Min/Load/Test/Calibration/Power-up/Keypad @
local/Keypad@power-up), Save Display Change (Enable/
Disable
), Passwords (Unpro-
tected/Main/Admin1/Admin2)
•
•
•
Series/Parallel (Table 2-12): Configuration (Standalone/Parallel/Series/Master 2X2/Master 3X2); for
parallel or series: Unit Type (Standalone/1 to+4/Slave #1 to #4) and Configuration: shows
Series or Parallel).
3.2.4.1
HOW TO MODIFY A PARAMETER
First access the parameter by accessing the proper menu as described above (PAR 3.2.4);
Tables 3-3 through 3-16 list the menu parameters. To modify a parameter listed in a menu or
submenu, proceed as follows:
1. Highlight the parameter using the
Y
and
U
keys.
2. When the desired choice is highlighted, press
!
to modify the active setting. The choices
are displayed with the active setting highlighted. In the case of numerals, the units digit is
highlighted.
Summary of Contents for BOP-ME 1KW
Page 2: ......
Page 20: ...xii BOP 1K 091719 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Page 42: ......
Page 64: ...2 22 BOP HIPWR 091719 FIGURE 2 11 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Page 65: ...BOP HIPWR 091719 2 23 FIGURE 2 12 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Page 76: ......
Page 161: ...BOP HIPWR 091719 3 85 FIGURE 3 29 STATUS REPORTING STRUCTURE...
Page 164: ......