BOP HIPWR 091719
3-59
3.5.3.3.3 CONFIGURE PROMPT MODE
Press
%
from the power-up screen, then highlight Interface Settings and press
!
to enter the
submenu (see Table 3-17). Highlight Prompt and press
!
, highlight the desired option and
press
$
to save, then press
%
to apply the changes (without saving for power-up) and exit, or
press
$
to save for power-up.
Enable
- Enables Serial Prompt (see PAR. 3.5.6.2.3 for a description of prompt mode).
Disable
- Disables Prompt. If both Serial XON/XOFF and Prompt functions are disabled, Echo
mode is the default (see PAR. 3.5.6.2.2 for a description of Xon/Xoff mode).
Echo
- Enables Echo (see PAR. 3.5.6.2.2) mode.
Enab+echo
- Enables Serial Prompt (see PAR. 3.5.6.2.3) and Echo (see PAR. 3.5.6.2.2)
modes. Prompt is returned when the unit is ready and any received characters are echoed back
to the sender.
3.5.3.4
LAN INTERFACE SETUP (ME MODELS ONLY)
Paragraphs 3.5.3.4.1 through 3.5.3.4.6 below describe the setup required for the BOP 1KW-ME
to communicate via the LAN interface using SCPI commands. Table 3-18 shows the menu for
LAN interface settings.
TABLE 3-18. LAN INTERFACE SETTINGS MENU
SETTING
CHOICES
(
BOLD
= Factory Default)
FUNCTION
MAC
---
Read-only display of MAC address for the unit.
IP Address
0.0.0.0
Allows IP address to be set manually if both DHCP and AUTO IP are
set to OFF. If either DHCP or AUTO IP are set to ON, provides read-
only display of automatically generated IP address.
Address Mask
255.255.255.0
Allows IP mask to be set manually if both DHCP and AUTO IP are set
to OFF. If either DHCP or AUTO IP are set to ON, provides read-only
display of automatically generated IP mask.
DHCP
ON
OFF
Set to ON allows automatic generation of IP address via DHCP server.
Set to OFF allows IP address and IP Mask to be set manually if AUTO
IP is also OFF
AUTOIP
ON
OFF
Set to ON allows automatic generation of IP address without DHCP. Set
to OFF allows IP address and IP Mask to be set manually if DHCP is
also OFF
Host
Name
Default =
XX YY SN
(e.g. 100_10_A654321)
XX = rated voltage, YY = rated current (Amps), SN = Unit serial num-
ber. Host Name can be changed as the user desires. Up to 12 ASCII
characters are permitted. See also PAR. B.164.
Index
0
Index number (1 through 99) is automatically assigned: 1 for first unit
found, subsequent identical units are assigned sequential index num-
bers to make the Host Name and Index a unique identifier. May be
changed to an unused number between 1 and 99 if desired.
NOTE: To restore all LAN interface settings defaults, press
%
from the power-up screen, highlight LAN Interface Settings, press
!
, then press
@
to restore defaults shown above in
BOLD
. Press
$
to save for power-up or
%
to apply the
changes (without saving for power-up) and exit.
Summary of Contents for BOP-ME 1KW
Page 2: ......
Page 20: ...xii BOP 1K 091719 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Page 42: ......
Page 64: ...2 22 BOP HIPWR 091719 FIGURE 2 11 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Page 65: ...BOP HIPWR 091719 2 23 FIGURE 2 12 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Page 76: ......
Page 161: ...BOP HIPWR 091719 3 85 FIGURE 3 29 STATUS REPORTING STRUCTURE...
Page 164: ......