BOP HIPWR 091719
3-43
TABLE 3-14. REVISIONS/TEST MENU
SETTING
CHOICES
(
BOLD
= Factory Default)
FUNCTION
Serial Number
(Cannot be highlighted)
nn
nn = unit serial number, also found on nameplate at rear panel.
Max Voltage
Max. Current
(Cannot be highlighted)
XX.0
YY.0
Displays rated output voltage and current of power supply. including all slaves
connected in parallel or series.
TEST
Display
Status (see NOTE below)
Shows primary (red, blue, green) and secondary (magenta, cyan, yellow) col-
ors) plus degrees of brightness. Press number keys 0 through 9 to change
contrast.
$
shows background color selected. Press
$
to change back-
ground. Lower half of screen shows colors used with selected background.
Press
%
to apply displayed conditions and exit.
Keypad
Status (see NOTE below)
Requires depressing keys indicated on LCD.
This test requires pressing every key on the keypad, plus moving the
ADJUST control clockwise and counterclockwise, with the ADJUST control
depressed and released. As the keys and control function pass the tests, the
corresponding function on the LCD is highlighted. When the last test is suc-
cessful, the LCD displays “passed.” The test must be completed within two
minutes, otherwise a “Failed” indication is displayed.
LAN
Status (see NOTE below)
Sends commands and data to LAN interface and verifies data is correct. If
LAN interface is not installed, test fails (see NOTE below).
Interface
Status (see NOTE below)
Automatic test, reports status messages (see NOTE below).
Serial
Status (see NOTE below)
Automatic test of serial port - requires installation of loop back test connector.
(see PAR. 3.5.6.4). Reports status messages (see NOTE below).
Analog
Status (see NOTE below)
Automatic test which does not affect unit output. Reports status messages
(see NOTE below).
Output
Status (see NOTE below)
WARNING: DANGEROUS VOLTAGES ARE PRESENT AT THE OUTPUT
TERMINALS: DO NOT TOUCH! DISCONNECT LOAD BEFORE RUNNING
THIS TEST.
Output is automatically programmed to +
E
Onom
then –
E
Onom
,
then to 0V. Test duration is less than 2 Seconds. Reports status messages
(see NOTE below).
Revisions
Display
Serial
GPIB
LAN
Analog
(Cannot be highlighted)
v.vv
w.ww
x.xx
y.yy
z.zz
Displays current firmware revision for display, serial, GPIB. LAN and analog
processors.
NOTE: Test status is as follows:
UNTESTED
Initial status when first entering menu.
TESTING
Test is running.
PASSED
Test was successful.
FAILED
Test failed.
FAIL EXT
SERIAL test failed - verify loop back connector installed (see PAR. 3.5.6.4).
Summary of Contents for BOP-ME 1KW
Page 2: ......
Page 20: ...xii BOP 1K 091719 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Page 42: ......
Page 64: ...2 22 BOP HIPWR 091719 FIGURE 2 11 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Page 65: ...BOP HIPWR 091719 2 23 FIGURE 2 12 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Page 76: ......
Page 161: ...BOP HIPWR 091719 3 85 FIGURE 3 29 STATUS REPORTING STRUCTURE...
Page 164: ......