AI 4/8-U
Kendrion Kuhnke Automation GmbH
164
17 May 2021
Technical Data
Analogue inputs ............................................. 8 single-ended or 4 differential
Measuring range ............................................
0 …10V, ± 5V, ± 10V, ± 2,5V
Resolution ...................................................... 13 bit
Start AD conversion ....................................... synchronised with DC / SM
Conversion time ............................................. 464 µs (if all channels are active)
Internal resistance ......................................... > 1M
Ω
Input filter cutoff frequency ............................ typ. 1kHz
Measuring error ............................................. < ±0.4%, typ. < ±0.2% of final value
Baud rate ....................................................... 100 Mbit/s
Controller ....................................................... ASIC ET1200
E-bus connector ............................................ 10-pole system plug in side wall
Terminating module ....................................... not required
IO/power connection ...................................... 18-pin plug
Power supply ................................................. 24 VDC -20% +25%
E-bus load...................................................... 190 mA
Part no. .......................................................... 694.441.52 13-Bit (CoE)
Approval:........................................................