Kendrion Kuhnke Automation GmbH
DI16/DO16
39
17 May 2021
LED "Power"
The LED labelled "Power" indicates the state of the I/O module's I/O power supply.
Information
The module is not monitored for low voltage states.
LEDs "Channel"
State
LED
Explanation
On
Green, on
Input signal TRUE / output enabled
Off
Off
Input signal FALSE / output disabled
Function
The DI16/DO16 module features 16 digital inputs and 16 digital outputs.
Variable
Variable
Data type
Explanation
DigitalInputn
BOOL
Digital input (n=0...15)
DigitalOutputn
BOOL
Digital output (n=0...15)
Technical Data
Digital inputs .................................................. 16
Rising delay ................................................... 1 ms / 5 ms (typically)
Signal level .................................................... Off:
-
3V … 5V (EN 61131-3, type 1)
On:
15V … 30V
Digital outputs ................................................ 16
Max. current ................................................... 0.5 A each
Max. total current ........................................... 8 A
IO/power connection ......................................
36-pin plug
Controller ....................................................... ASIC ET1200
Baud rate ....................................................... 100 Mbit/s
E-bus connector ............................................ 10-pole system plug in side wall
Terminating module ....................................... not required
Power supply ................................................. 24 VDC -20% +25%
E-bus load...................................................... 135 mA
Part no.
Kuhnke FIO DI16/DO16 5ms/0.5A ................ 694.450.01
Kuhnke FIO DI16/DO16 1ms/0.5A. ............... 694.450.03
Approval:........................................................