Kendrion Kuhnke Automation GmbH
AI 8 Pt/Ni/Tc
203
17 May 2021
It can only be calibrated once because the calibration values are kept on memory.
The calibration objects (2010:n; 2011:n and 2012:n) in the Startup Parameters are intended for internal use
only.
Object Dictionary
Index
Name
Type
Default
Min Max
Access
1000
Device Type
UINT32 0x40191
RO
1001
Error Register
UINT8
RO
1008
Device Name
String
AI8_Pt/Ni/Thermo
RO
1009
Hardware Version
String
1.00
RO
100A
Software Version
String
1.00
RO
1018
Identity Object
Array
1018, 0
Number of Entries
UINT8
4
RO
1018, 1
Vendor Id
UINT32 0x0048554B
RO
1018, 2
Product Code
UINT32 185346
RO
1018, 3
Revision Number
UINT32 1
RO
1018, 4
Serial Number
UINT32
RO
2000
Sensor Type
Array
2000, 0
Number of Entries
UINT8
8
RO
2000, 1
Sensor0
UINT8
Off
Off (0),
Internal (1),
PT100 (2),
PT1000 (3),
NI100 (4),
NI1000 (5),
Thermo_K (6),
Thermo_J (7),
RW
2000, 2
Sensor1
UINT8
Off
Off,
Internal,
PT100,
PT1000,
NI100,
NI1000,
Thermo_K,
Thermo_J,
RW
2000, 3
Sensor2
UINT8
Off
Off,
Internal,
PT100,
PT1000,
NI100,
NI1000,
Thermo_K,
Thermo_J,
RW
2000, 4
Sensor3
UINT8
Off
Off,
Internal,
PT100,
PT1000,
NI100,
NI1000,
RW