Mix 02
Kendrion Kuhnke Automation GmbH
290
17 May 2021
5.6 Mixed Modules
5.6.1 MIX 02
Terminals
IO connection, male 36-pin
Side
Trm.
Signal
Explanation
left
0..15
DO8..DO23
digital outputs 8..23
16, 17
+24VDC, 0V
module power supply to CPU
right
0..7
DO0..DO7
digital outputs 1..7
8..11
AI0..AI3,
DI0..DI3
analogue inputs (optionally used as
DI)
12
DI4
digital input DI
13
DI5
C_cycle DI
counting cycle input (rising
edge)
14
DI6
C_Dir
DI
counting
direction
FALSE: up
TRUE: down
15
DI7
C_Clear DI clear counter (rising edge)
16, 17
+24VDC, 0V
IO power supply
Operative earth / shield of analogue and counter lines
section Earth
I/O connection
Front view of I/O module MIX 02