D3-DA 3xx/x
EC directives and standards
Project engineering manual V1.07
104
© KEBA
13.2.4
Environmental and surrounding conditions
EN 61800-2: 2015
Adjustable speed electrical power drive sys-
tems - Part 2: General requirements; rating
specifications for low voltage adjustable fre-
quency a.c. power drive systems
13.3
CE marking
The D3-DA 3xx/x meets the requirements for installation in a machine or
plant in the context of the Machinery directive 2006/42/EG and the Low volt-
age directive 2014/35/EU. The D3-DA 3xx/x is accordingly CE marked. The
D3-DA 3xx/x axis modules in a group with the D3-DP 3xx/x supply modules
and on observing the installation instructions and on the usage of cabels and
accessories suggested in chapters
meet the requirement of EMC directives 2014/30/EU.
For validity of CE declaration also the data of the mains filters (for number
max. allowed axes and max. allowed complete cable length for all axes)
must be considered.
13.4
UL certification
Information
The following requirements must be observed for a valid UL mark.
Common terms to comply with the UL certification (UL 61800-5-1) for all the
sizes of D3-DA 3xx/x.
Multiple rated equipment. Operation only within the technical ratings of the
drive, details see "Technical data".
Ensure that surrounding air temperature exceeds not the maximum appro-
bate ambient temperature (see table below in this chapter).
Use in a pollution degree 2 environment according to IEC60664-1 only. This
means device shall be mounted in a suitable switchgear cabinet.
Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance to the
manufacturer instructions, National Electrical Code and any additional local
codes.
Use the following UL-certified device wiring (mains, motor and control ca-
bles) only:
●
Copper conductors rated min. 75 °C.
●
Recommended terminal connectors and specified tightening torques for
terminals (see "Connections and wiring")