Connections and wiring
Project engineering manual V1.07
52
© KEBA
or with a protective conductor with enough crosssection. Make a con-
nection from one of the devices to the PE rail (main earth) in the cabi-
net.As the leakage current >3.5 mA, the following applies to the PE con-
nection: Use protective conductors with the same crosssection as the
mains cables. If the crosssection of the mains cable is ≤10 mm² the PE
connections are to be doubled, or a copper cable with a minimum cross-
section 10 mm
2
is to be laid.
2) Also connect the PE-conductor terminals of all other components, such
as main filters etc. in a star configuration with the PE bar (main earth) in
the cabinet.
These further components are only required for the D3-DP 3xx/x supply
module.
Information
Material of the cooler or cold plate: aluminium with high conductive trans-
parent passivation.
Protective earth conductor with mains cable crosssection ≥ 10
mm²
Fig. 6-29: Protective earth conductor
1
... D3-DU 3xx/x control module
2
... D3-DP 3xx/x supply module
3
... D3-DA 3xx/x axis module size 1
4
... D3-DA 3xx/x axis module size 2