22
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
UNIT DIMENSIONS 039 TO 090
�
BACK
LEFT
FRONT
RIGHT
B
E
G
F
H
D
C
2"
1
1 3
A
1
I
Notes:
A. Dimensions do not include handles, latches, lifitng lugs or fastener extensions.
B. All dimensions are ± 0.25".
C. Condenser water supply/return can be located on the left or the right hand side of the unit (right hand shown).
2
1
1
1
1
1
1
FILTER
SECTION
COIL
SECTION
FAN
SECTION
RETURN AIR
SUPPLY AIR
OPERATOR
INTERFACE
VARIABLE
FREQUENCY
DRIVE
CONDENSATION DRAIN CONNECTION L
CONDENSATION WATER RETURN M
CONDENSATION WATER SUPPLY M
JXK
14-1/2"
5-5/8"
5-1/8"
5"
Ø7/8"
POWER CONNECTION
(RIGHT HAND SIDE)
11-3/8"
1-1/2"
16-1/4"
Model YSWU
039
048
050 &
055
072
079
060
& 090
CFM Range
10,700– 12,700– 14,000– 14,700– 19,100– 21,000–
16,000
19,000
24,000
22,000
28,700
36,000
Tonnage Range
35–55
40–65
40–80
50–75
65–100 70–120
Unit Style
Modular Modular
New/Retrofit
Modular
New/Retrofit New/Retrofit
A
1
Fan Section Width
34
34
CF
34
CF
CF
B
1
Coil Section Width
34
34
CF
34
CF
CF
C
1&3
Installed Width
68
68
82
68
82
94
D
Discharge Opening Width
20
20
24
20
24
24
NOTES
E
Discharge Opening Length 64
76
72
84
90
112
(see page 23)
F
1
Installed Height
78
78
98
78
98
98
G
1
Electrical Section Width
19 5/8
19 5/8
19 5/8
19 5/8
19 5/8
19 5/8
H
Base Length (no panels)
74
86
82
98
96
118
I
2
Installed Length
74
86
82
98
96
118
J
Inlet Height
58 1/2
58 1/2
73 1/2
58 1/2
73 1/2
73 1/2
K
Inlet Length
60
60
80
60
80
80
L
Drain Connection
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
M
Condenser Water Supl/Ret. 2 5/8
2 5/8
2 5/8
3 1/8
3 1/8
3 1/8
All dimensions in inches
LDO10369
Due to the dedication of continuous product improvement and enhancements, the information/dimensions provided are subject to
change without notice.
Installation
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...