64
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
FORCED OUTPUTS
This feature of the Keypad / Display is intended as
a service tool for the experience Service Technician.
The feature allows all the binary and analog outputs to
be “forced” on. This allows the experienced Service
Technician to verify the outputs from the control and
the operation of the controlled components.
The following sequence would be required to use this
feature:
•
Place the “On / Auto / Off” toggle switch in the
Off position.
•
From the Run Status screen, use the right arrow
key > to scroll down to Forced Outputs.
•
When Forced Outputs is surrounded by brackets,
press the ENTER key.
•
The Password screen will appear. (Ask startup
technician for password).
•
In the Password screen, use the INC and DEC
keys to enter your administrator password. Use
the right arrow key > to move the cursor. After
entering the password, press the ENTER key >.
TABLE 17 – FORCED ON PARAMETERS
DESCRIPTION
O U T P U T
LOCATION
O U T P U T
TYPE
CAUTION
CV Fan
DO-3
Binary
Never turn on CV Fan and VAV Fan at the same time
VAV Fan
DO-2
Binary
Never turn on VAV Fan and CV Fan at the same time
Pump Out
DO-6
Binary
Starts condenser water pump
Aux Fan Out
DO-5
Binary
Box Open
DO-4
Binary
Used to send remote signal to open VAV boxes
Comp A
Exp DO-1
Binary
Never operate the compressor for more than ten seconds in this mode
Comp B
Exp DO-2
Binary
Never operate the compressor for more than ten seconds in this mode
Comp C
Exp DO-3
Binary
Never operate the compressor for more than ten seconds in this mode
Comp D
Exp DO-4
Binary
Never operate the compressor for more than ten seconds in this mode
Alarm Output
DO-1
Binary
Can be used by the field to identify the unit is in Fault or Alarm mode
Heat 1 / Close
Exp DO-8
Binary
Used to energize the first stage of staged heat or to close the valve with Tri State Heat
Heat 2 / Open
Exp DO-7
Binary
Used to energize the second stage of staged heat or to open the valve with Tri State Heat
Cond Valve
AO-4
Analog
Sends 0 to 10 volt signal to condenser water valve
VFD Speed
AO-3
Analog
Sends 0 to 10 volt signal to VFD
Bypass Damp
(FlexSys units only) AO-2
Analog
Sends 0 to 10 volt signal to modulating heat valve
Econ Valve
AO-1
Analog
Sends 0 to 10 volt signal to Econ water valve or air damper motor
Heat Valve
AO-2
Analog
Sends 0 to 10 volt signal to modulating heat valve
•
Use the right arrow key > to scroll through the
Forced Outputs.
•
When you find the parameter to “Force On” the
following will appear on the screen [Unfrc].
•
Press the ENTER key and then use the INC key
to change to [Force] and press the ENTER key
again.
•
Use the right arrow key > to move the brackets
to [Off].
•
Press the ENTER key and use the INC key to
change Off to On
•
The output will now be “Forced On”
•
DO NOT LEAVE OUTPUTS FORCED
ON – WHEN OPERATION IS VERIFIED
CHANGE THE PARAMETER BACK TO
“Off” and “Unfrc”.
Table 17 identifies the parameters that can be “Forced
On”.
User Interface Control Center
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...