120
JOHNSON CONTROLS
FORM 145.05-NOM1 708)
TABLE 27 – CONSTANT VOLUME / VARIABLE AIR VOLUME MAIN CONTROL BOARD *
BOARD
CONNECTOR
POINT
I/O TYPE
INPUT DEVICE
INPUT
IN-1
ANALOG INPUT
SUPPLY AIR TEMP
THERMISTOR
IN-2
ANALOG INPUT
MIXED AIR TEMP
THERMISTOR
IN-3
ANALOG INPUT
DUCT STATIC PRESSURE 1
4 – 20 MA
IN-4
ANALOG INPUT
DUCT STATIC PRESSURE 2
4 – 20 MA
IN-5
ANALOG INPUT
VFD SPEED (NOT USED)
4 – 20 MA
IN-6
NOT USED
IN-7
BINARY INPUT
AIR PROVING SWITCH
DRY CONTACT 5 VDC VOLTAGE
IN-8
BINARY INPUT
DUCT HIGH STATIC
DRY CONTACT 5 VDC VOLTAGE
IN-9
ANALOG INPUT
RETURN AIR TEMPERATURE
THERMISTOR
1N-10
ANALOG INPUT
OUTSIDE AIR TEMPERATURE
THERMISTOR
AO-1
ANALOG OUTPUT WATER SIDE ECONOMIZER OUTPUT
2 – 10 VDC
AO-2
ANALOG OUTPUT AIR SIDE ECONOMIZER OUTPUT
2 – 10 VDC
AO-3
ANALOG OUTPUT SUPPLY FAN VFD (VAV UNITS ONLY)
0– 10 VDC
AO-4
ANALOG OUTPUT CONDENSER WATER VALVE / CONDENSER BYPASS VALVE
2 – 10 VDC
DO-1
BINARY OUTPUT
ALARM OUTPUT
DRY CONTACT
DO-2
BINARY OUTPUT
VAV FAN OUTPUT
DRY CONTACT
DO-3
BINARY OUTPUT
CV FAN OUTPUT / SUPPLY FAN BYPASS
DRY CONTACT
DO-4
BINARY OUTPUT
VAV BOX COMMAND
DRY CONTACT
DO-5
BINARY OUTPUT
FAN START
DRY CONTACT
DO-6
BINARY INPUT
PUMP START
DRY CONTACT
* Check the wiring diagram in the unit for the exact location of the input and outputs as they may change based
on the configuration of the unit.
Service
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...