105
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
POINT ID
POINT DESCRIPTION
N2
OBJECT
READ
( R )
WRITE
( W )
VALUE
RANGE
(ANALOG
ONLY)
UNIT
(ANALOG
ONLY)
IN-
STANCE
NUMBER
COMMENTS
UNIT
ENABLE
NETWORK UNIT START
1 = ENABLE
0 = DISABLE
BYT44
R,W
-
-
15001
SATACSP
SUPPLY AIR COOLING
TEMPERATURE SET
POINT
ADF45
R/W
48.0
– 70.0
DEG F
16001
RATACSP
RETURN AIR COOLING
TEMPERATURE SET
POINT
ADF46
R/W
55.0
– 80.0
DEG F
16002
SATHTSP
SUPPLY AIR HEATING
TEMPERATURE SET
POINT
ADF47
R/W
80.0
– 125.0
DEG F
16003
RATHTSP
RETURN AIR HEATING
TEMPERATURE SET
POINT
ADF48
R/W
50.0
– 80.0
DEG F
16004
O/A MIN POS
OUTDOOR AIR MINIMUM
POSITION SETPOINT
ADF49
R/W
0 – 100
%
16012
ONLY WITH AIR SIDE ECONO-
MIZER
SAP SP
DUCT STATIC PRESSURE
SET POINT
ADF50
R/W
0.0 – 2.0
IN OF WC
16013
ONLY WITH VAV OR FLEXSYS
AI = ANALOG INPUT
BI = BINARY INPUT
AO = ANALOG OUTPUT
BO = BINARY OUTPUT
ADF = ANALOG DATA FLOAT
ADI = ANALOG DATA INTEGER
BYT = DATA BYTE
TABLE 19 – N2 POINTS LIST