The parameters in Table 16 can be programmed using the Setpoint screen.
TABLE 16 – SETPOINT SCREEN PARAMETERS
DESCRIPTION
OPTIONS
DEFAULT VALUE
UNIT ENABLE
ON / OFF
OFF
MIN DX PRS DROP (FLEXSYS UNITS ONLY)
0.2" WC – 1.0" WC
0.5" WC
POA DX PRS DROP (FLEXSYS UNITS ONLY)
.06" WC TO 1.0" WC
0.1" WC
AC – S/A DEW EN (FLEXSYS UNITS ONLY)
ON / OFF
ON
AC-S/A DEW MIN (FLEXSYS UNITS ONLY)
40.0° F – 90.0° F
48.0° F
AC – S/A DEW MAX (FLEXSYS UNITS ONLY)
40.0° F – 90.0° F
60.0° F
AC – S/A DEW DIF (FLEXSYS UNITS ONLY)
2.0° F – 10.0° F
5.0° F
AC-S/A TEMP EN
ON / OFF
ON
ECON-S/A TMP EN
ON / OFF
ON
AC/ECON-S/A SP
40° F – 90° F
55° F
AC-R/A TEMP EN
ON / OFF
ON
ECON-R/A TMP EN
ON / OFF
OFF
AC/ECON – R/A SP
40° F – 90° F
75° F
HEAT – S/A TMP EN
ON / OFF
OFF
HEAT S/A TMP SP
40° F – 115° F
110° F
HEAT R/A TMP EN
ON / OFF
OFF
HEAT R/A TMP SP
40° F – 90° F
72° F
FAN-VAV/CV EN
CV / VAV
VAV
# OF SP SENSORS
1, 2
1
SP CALC METHOD
1 – HIGH/2-AVG/3-LOW
2
FAN SP BAS EN (FLEXSYS UNITS ONLY)
ON / OFF
OFF
VFD SP % BY BAS (FLEXSYS UNITS ONLY)
0% TO 100%
0 %
FAN-S/A PRES SP
0.0" WC TO 2.0" WC
1.0
O/A ECON EN
ON / OFF
OFF
WATER ECON EN
ON / OFF
OFF
COND VALVE MIN
0% TO 100%
15%
BYPASS VAL MAX
0% TO 100%
25%
O/A DAMPER MIN
0 % – 100 %
15%
HT STG –1/TRI-2
1 – STAGED HEAT/ 2- TRI STATE HEAT
1
HEAT STG 0 OR 2
0 OR 2
0
COMP STG 4 OR 6
4 OR 6
6
ECON VALVE MIN
0% TO 100%
0%
6
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...