102
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
TABLE 19 – N2 POINTS LIST
POINT ID
POINT DESCRIPTION
N2
OBJECT
READ
( R )
WRITE
( W )
VALUE
RANGE
(ANALOG
ONLY)
UNIT
(ANALOG
ONLY)
IN-
STANCE
NUMBER
COMMENTS
ON SWCH
UNIT ON SWITCH STATUS
1 = ON
0 = OPEN
BI1
R
-
-
12001
OFF SWCH
UNIT OFF SWITCH
1 = STOPPED – ACTIVE
0 = UNIT OPERATION
ALLOWED – INACTIVE
BI2
R
-
-
12002
SAFE IN
EXTERNAL SAFETY
1 = NORMAL
0 = FAULT
BI3
R
-
-
12003
AIR FLOW
SWCH
AIR FLOW SWITCH
STATUS
1 = CLOSED
0 = OPEN
BI4
R
-
-
12004
DUCT HI
STATIC
STATUS OF THE DUCT
STATIC HIGH LIMIT
SWITCH
1 = NORMAL – ACTIVE
0 = FAULT – INACTIVE
BI5
R
-
-
12005
FREEZE
STAT
FREEZE STAT INPUT
1 = CLOSED – ACTIVE
0 = OPEN – INACTIVE
BI6
R
-
-
12006
ONLY WITH HYDRONIC HEAT
DFS
DIRTY FILTER SWITCH
INPUT
1 = DIRTY – ACTIVE
0 = NORMAL – INACTIVE
BI7
R
-
-
12007
S/A TEMP
SUPPLY AIR
TEMPERATURE
AI8
R
0 – 120
DEGF
13001
M/A TEMP
MIXED AIR
TEMPERATURE
AI9
R
0 – 120
DEG F
13002
R/A TEMP
RETURN AIR
TEMPERATURE
AI10
R
0 – 120
DEG F
13003
E/W TEMP
ENTERING CONDENSER
WATER TEMP
AI12
R
0 – 120
DEG F
13004
L/W TEMP
LEAVING CONDENSER
WATER TEMP
AI13
R
0 – 120
DEG F
13005
FAN SPEED
ANALOG OUTPUT TO THE
SUPPLY FAN VFD IN %
AI15
R
0-100
%
13006
ONLY WITH VAV OR FLEXSYS
O/A TEMP
OUTDOOR AIR
TEMPERATURE
AI11
R
0 – 120
DEG F
13019
ONLY WITH AIR SIDE ECONO-
MIZER
DUCT STAT 1
OUT
DUCT STATIC 1 INPUT
AI16
R
0 – 2
INC WC
16102
ONLY WITH VAV OR FLEXSYS
DUCT STAT 2
OUT
DUCT STATIC 2 INPUT
AI17
R
0 – 2
INC WC
16103
ONLY WITH VAV OR FLEXSYS
Continued on next page
User Interface Control Center
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...