122
JOHNSON CONTROLS
FORM 145.05-NOM1 708)
TABLE 29 – FLEXSYS MAIN CONTROL BOARD *
BOARD
CONNECTOR
POINT
I/O TYPE
INPUT DEVICE
INPUT
IN-1
ANALOG INPUT
SUPPLY AIR TEMP
THERMISTOR
IN-2
ANALOG INPUT
MIXED AIR TEMP
THERMISTOR
IN-3
ANALOG INPUT
UNDER FLOOR STATIC PRESSURE
4 – 20 MA
IN-4
ANALOG INPUT
DX COIL LEAVING TEMPERATURE
4 – 20 MA
IN-5
ANALOG INPUT
VFD SPEED (NOT USED)
4 – 20 MA
IN-6
ANALOG INPUT
SLAB TEMPERATURE
THERMISTOR
IN-7
ANALOG INPUT
COIL DIFFERENTIAL PRESSURE
4 – 20 MA
IN-8
BINARY INPUT
DUCT HIGH STATIC
DRY CONTACT 5 VDC VOLTAGE
IN-9
ANALOG INPUT
RETURN AIR TEMPERATURE
THERMISTOR
1N-10
ANALOG INPUT
SUPPLY AIR HUMIDITY
4 – 20 MA
AO-1
ANALOG OUTPUT WATER OR AIR SIDE ECONOMIZER OUTPUT
2 – 10 VDC
AO-2
ANALOG OUTPUT BY PASS DAMPER
2 – 10 VDC
AO-3
ANALOG OUTPUT SUPPLY FAN VFD
0 – 10 VDC
AO-4
ANALOG OUTPUT CONDENSER WATER VALVE / CONDENSER BYPASS VALVE
2 – 10 VDC
DO-1
BINARY OUTPUT ALARM OUTPUT
DRY CONTACT
DO-2
BINARY OUTPUT VAV FAN OUTPUT
DRY CONTACT
DO-3
BINARY OUTPUT CV FAN OUTPUT / SUPPLY FAN BYPASS
DRY CONTACT
DO-4
BINARY OUTPUT VAV BOX COMMAND
DRY CONTACT
DO-5
BINARY OUTPUT FAN START
DRY CONTACT
DO-6
BINARY INPUT
PUMP START
DRY CONTACT
* Check the wiring diagram in the unit for the exact location of the input and outputs as they may change based
on the configuration of the unit.
Service
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...