23
2
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
TABLE 7 – REFRIGERANT CHARGE DATA
Continued on next page
MODEL #
# EVAP
COIL
ROWS
COMP A
COMP B
COMP C
COMP D
NOM HP
R22
CHARGE
LBS
NOM HP
R22
CHARGE
LBS
NOM HP
R22
CHARGE
LBS
NOM HP
R22
CHARGE
LBS
DVW012
4
7
8
4
7.5
-
-
-
-
DVW012
6
7
9.5
4
9
-
-
-
-
DVW012
4
10
9.5
4
7.5
-
-
-
-
DVW012
6
10
11
4
9
-
-
-
-
DVW012
4
10
9.5
7
8.5
-
-
-
-
DVW012
6
10
11
7
9.5
-
-
-
-
DVW012
4
12
10
7
8.5
-
-
-
-
DVW012
6
12
11.5
7
9.5
-
-
-
-
DVW016
4
7
9
4
8.5
-
-
-
-
DVW016
6
7
10.5
4
10
-
-
-
-
DVW016
4
10
10
4
8
-
-
-
-
DVW016
6
10
12
4
10
-
-
-
-
DVW016
4
10
10.5
7
9
-
-
-
-
DVW016
6
10
12
7
11
-
-
-
-
DVW016
4
12
11
7
9
-
-
-
-
DVW016
6
12
13
7
11
-
-
-
-
DVW016
4
15
12
7
9
-
-
-
-
DVW016
6
15
14
7
11
-
-
-
-
DVW016
6
15
14
10
12.5
-
-
-
-
DVW021
4
7
9.5
4
9.5
-
-
-
-
DVW021
4
10
11.5
4
9.5
-
-
-
-
DVW021
6
10
13.5
4
11.5
-
-
-
-
DVW021
4
10
11.5
7
10
-
-
-
-
DVW021
6
10
13.5
7
12
-
-
-
-
DVW021
4
12
14
7
12
-
-
-
-
DVW021
6
12
14
7
12
-
-
-
-
DVW021
4
15
12
7
10
-
-
-
-
DVW021
6
15
14
7
12
-
-
-
-
DVW021
4
15
13
10
11.5
-
-
-
-
DVW021
6
15
15.5
10
14
-
-
-
-
DVW021
4
15
13
12
12
-
-
-
-
DVW021
4
20
15.5
12
12
-
-
-
-
DVW021
6
20
20
12
12
-
-
-
-
DVW021
6
25
19
12
14.5
-
-
-
-
DVW025
4
10
10
4
4
-
-
-
-
DVW025
6
10
15
4
13
-
-
-
-
DVW025
4
10
12
7
11
-
-
-
-
DVW025
6
10
15
7
13.5
-
-
-
-
DVW025
4
12
13
7
11
-
-
-
-
DVW025
6
12
15.5
7
13.5
-
-
-
-
DVW025
4
15
14
7
11
-
-
-
-
DVW025
6
15
16.5
7
13.5
-
-
-
-
DVW025
4
15
14
10
12.5
-
-
-
-
DVW025
6
15
16.5
10
15
-
-
-
-
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...