TABLE 18 – BACnet MS/TP points (CONT.)
Point ID
Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
DxPrsMn
Minimum Pressure Drop
Across the Evaporator Coil to
Prove Air Flow
BAV
R/W
0.06 – 1.0
in of wc
16023
Only with FlexSys
E/W Econ En
BBV
15008
Not Applicable
E/W Min
BAV
16017
Not Applicable
E/W Mod
BAO
14004
Not Applicable
E/W Rat Mod
BAV
16114
Not Applicable
E/W Sat Mod
BAV
16113
Not Applicable
E/W Temp
BAI
13004
Not Applicable
E/WSadMod
Economizer PID Output Based
on Dew Point Temp
BAV
R
0 – 100
%
16124
Only with
Economizer,
FlexSys with Dew
Point Control
EcRat Enable
Economizer Return Air Temp
Control:
1 = Enabled
0 = Disabled
BBV
R/W
-
-
15007
EcSad Enable
Economizer Dew Point Temp
Control:
1 = Enabled
0 = Disabled
BBV
R/W
-
-
15009
Only with FlexSys
EcSat Enable
Economizer Supply Air Temp
Control:
1 = Enabled
0 = Disabled
BBV
R/W
-
-
15006
Fan Bp/Exh En
Status of the Constant Volume
Fan Output:
1 = On – Active
0 = Off – Inactive
BBO
R/W
-
-
11001
Fan Out
Status of the Fan Out Dry
Contact:
1 = On Active
0 = Off – Inactive
BBO
R/W
-
-
11004
Fan Speed
Analog Output to the Supply
Fan VFD in Volts
BAI
R
0-10
Volts
13006
Only with VAV or
FlexSys
Fan VFD En
Binary Output to Energize the
Supply Fan VFD:
1 = On Active
0 = Off – Inactive
BBO
R/W
-
-
11002
Only with VAV or
FlexSys
FanFlt
Indoor Fan Failure Alarm:
1 = Fault
0 = No Fault
BBV
R
-
-
15113
FC Comp A
BBV
-
-
15506
Not Applicable
FC Comp B
BBV
-
-
15507
Not Applicable
6
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...