28
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
For unit in the cooling mode:
MOP = 2.25 (largest motor RLA or FLA) + other
loads + 2 amps.
For units in the heating mode:
With Electric Heater KW 50 KW or less:
MOP = 2.25(electric heat FLA + supply fan
motor amps) + 2 amps.
With Electric Heater KW greater than 50KW:
MOP = 2.25 (supply fan motor amps) + elec-
tric heat FLA + 2 amps.
HORSEPOWER
208/60/3 FLA
230/60/3 FLA
460/60/3 FLA
575/60/3 FLA
3
8.8
8.6
4.3
3.8
5
14.2
13.2
6.6
5.9
7.5
21.4
19.6
9.8
8.4
10
28.6
26.4
13.2
10.4
15
42.0
39
19.5
16.0
20
55.0
50.0
25.0
20.0
25
66.0
60.0
30.0
26.0
30
80.0
70.0
35.0
28.5
40
110.0
93.0
46.0
36.1
50
137.0
118.0
59.0
46.5
TABLE 8 – FAN MOTOR DATA
TABLE 9 – COMPRESSOR MOTOR DATA
HP
208/60/3
230/60/3
460/60/3
575/60/3
RLA
LRA
RLA
LRA
RLA
LRA
RLA
LRA
4
12.1
91.0
10.9
91.0
5.5
50.0
4.4
37.0
7
19.6
164.0
17.7
164.0
9.7
100.0
7.8
80.0
10
31.2
239.0
28.2
239.0
14.1
125.0
11.3
80.0
12
34.4
245.0
31.1
245.0
15.5
113.0
12.5
100.0
15
42.1
425.0
38.0
425.0
19.0
187.0
15.2
148.0
20
57.5
500.0
52.0
500.0
26.0
250.0
20.8
200.0
25
74.4
500.0
67.2
500.0
32.0
250.0
25.6
200.0
Contact the factory for electric heat full load amp
data.
Field Control Wiring
The unit has three sets of 24-volt AC/DC dry contacts
rated at 3 amps maximum that are normally open. The
following is a description of each of the contacts.
Pump Start
Contact DO-6 on the Unit Control Board closes
whenever the Unit Control is in the on mode, either by
the ON switch, the internal schedule, or a communicated
ON input. This contact can be used to energize the
condenser water pump. The connection point for this
feature is terminals 9 and 10 of the low voltage terminal
block.
Installation
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...