89
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
Continued on next page
TABLE 18 – BACnet MS/TP points (CONT.)
Point ID
Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
SadAcMx
Maximum Supply Air
Temperature for Dew Point
Control
BAV
R / W
40.0
– 90.0
Deg F
16022
Only with FlexSys
with Dew Point
Control
Safe In
External Safety:
1 = Normal
0 = Fault
BBI
R
-
-
12003
Sap SP
Duct Static Pressure Set Point
BAV
R/W
0.0 – 2.0
In of wc
16013
Only with VAV or
FlexSys
SatAcSp
Supply Air Cooling
Temperature Set Point
BAV
R/W
48.0
– 70.0
Deg F
16001
SatHtSp
Supply Air Heating
Temperature Set Point
BAV
R/W
80.0
–125.0
Deg F
16003
SATURDAYSCHED1
Turns Saturday On / Off for
Schedule 1:
1 = On – Active
0 = Off – Inactive
BBV
R/W
-
-
879
SATURDAYSCHED10
Turns Saturday On / Off for
Schedule 10:
1 = On – Active
0 = Off – Inactive
BBV
R/W
-
-
979
SATURDAYSCHED11
Turns Saturday On / Off for
Schedule 11:
1 = On – Active
0 = Off – Inactive
BBV
R/W
-
-
990
SATURDAYSCHED12
Turns Saturday On / Off for
Schedule 12:
1 = On – Active
0 = Off – Inactive
BBV
R/W
-
-
1001
SATURDAYSCHED13
Turns Saturday On / Off for
Schedule 13:
1 = On – Active
0 = Off – Inactive
BBV
R/W
-
-
1012
SATURDAYSCHED14
Turns Saturday On / Off for
Schedule 14:
1 = On – Active
0 = Off – Inactive
BBV
R/W
-
-
1023
SATURDAYSCHED15
Turns Saturday On / Off for
Schedule 15:
1 = On – Active
0 = Off – Inactive
BBV
R/W
-
-
1033
SATURDAYSCHED16
Turns Saturday On / Off for
Schedule 16:
1 = On – Active
0 = Off – Inactive
BBV
R/W
-
-
1044
6
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...