FORM 145.05-NOM1 (708)
MENU ITEM
DEFINITION
BYPASS DAMP
This item is used to force an analog output to the bypass damper (FlexSys units
only).
BYPASS VAL MAX
When the unit is equipped with a by-pass valve this item is used to program the
maximum position set point for the by-pass valve.
CALC DUCT STATIC
When multiple duct static transducers are used this is the derived duct static
input used by the Unit Controller for the control of the supply fan VFD.
COIL DIF STATIC
This is the pressure drop across the evaporator coil (FlexSys units only).
COIL LEAV TEMP
This is the temperature of the air leaving the evaporator coil (FlexSys units
only).
COMP A
This item is used to force the binary output to compressor A to ON.
COMP A DISCH
This is the discharge pressure for compressor system A.
COMP A EN
This gives the status of the digital output to compressor A.
COMP A SUCT
This is the suction pressure for compressor system A.
COMP B
This item is used to force the binary output to compressor B to ON.
COMP B DISCH
This is the discharge pressure for compressor system B.
COMP B EN
This gives the status of the digital output to compressor B.
COMP B SUCT
This is the suction pressure for compressor system B.
COMP C
This item is used to force the binary output to compressor C to ON.
COMP C DISCH
This is the discharge pressure for compressor system C.
COMP C EN
This gives the status of the digital output to compressor C.
COMP C SUCT
This is the suction pressure for compressor system C.
COMP D
This item is used to force the binary output to compressor D to ON.
COMP D DISCH
This is the discharge pressure for compressor system D.
COMP D EN
This gives the status of the digital output to compressor D.
COMP D SUCT
This is the suction pressure for compressor system D.
COMP STG 4 OR 6
This is the suction pressure for compressor system D.
COND PID
This is the condenser water PID loop generated by comparing the highest com-
pressor discharge pressure to the discharge pressure set point.
COND PUMP OUT
This gives the status of the digital output to the condenser water pump.
COND VALVE MIN
This item is used to program the minimum position set point for the condenser
water valve.
COND VLV
This item is used to force an analog output to the condenser water valve.
COND VLV MOD
This is the analog output to the condenser water valve.
CV FAN
This item is used to force the binary output to the constant volume fan to ON.
CV FAN ENABLE
This gives the status of the digital output for a constant volume fan.
DDC OFF SWITCH
This indicates if the binary input from the OFF contact of the ON/OFF/AUTO
switch is energized or not.
DDC ON SWITCH
This indicates if the binary input from the ON contact of the ON/OFF/AUTO
switch is energized or not.
TABLE 20 – DEFINITIONS (CONT.)
Parameter Description and Options
Continued on next page
Summary of Contents for York VERSECON YSWD 012
Page 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...